5.4.4 Battery Cabinets

Although the individual batteries are sealed and require only minimal maintenance, the batteries should be
given a periodic inspection and electrical check. Checks should be performed annually to ensure years of
trouble-free service. Tightness of battery terminal connections should be tested to recommended torque
values. Battery Service Agreements are available through OnLine Power. Although the individual batteries
are sealed and require only minimal maintenance, the batteries should Customer Service and Support at 1-
800-PWR-SRVC (800-797-7782)...

5.4.5 Power Connections

• Check for corrosion and connection integrity. Visually inspect wiring for discolored or cracked

insulation. Clean and / or re-torque as required.

• All Battery Terminal connections shall be initially torqued to 75 in/lbs. Subsequent re-torquing shall be

to 65 in/lbs.

5.4.6 Battery Terminals

• Check for discoloration, corrosion, and connection integrity. Clean and tighten as necessary. Note:

Initial Torque Values are greater than re-torque values.

To access battery terminals, remove the top strapping material located at the lower front of the battery
shelf. Pull the battery forward to access the battery connections. Disconnect the cables connected to
the battery. Once disconnected, insulate the cables to prevent accidental shorts. (Use a protective
boot or electrical tape.) Before replacing the battery connections you must clean and re-torque the
connection hardware.

OnLine Power Customer Service Personnel must approve non-Standard Batteries. Please call at 1-
800-PWR-SRVC (800-797-7782).

5.5

ONLINE POWER CUSTOMER SERVICE AND SUPPORT

Start-up, UPS Maintenance, battery maintenance, and preventative maintenance programs are available
through your OnLine Power sales representative or through OnLine Power Customer Service & Support.

5.5.1 Start-Up Services

Various Start-up services are available. See your sales representative or telephone OnLine Power
Customer Service at 1-800-PWR-SRVC (800-797-7782).

5.5.2 Maintenance Agreements

Standard Full Service, 24/7 Full Service, and Extended On or OFF Site Maintenance agreements are
available. See your sales representative or telephone OnLine Power Customer Service at 1-800-PWR-
SRVC (800-797-7782).

5.5.3 Warranties

Contact OnLine Power Customer Service and Support at 1-800-PWR-SRVC (800-797-7782) if you have
any questions regarding the warranty on your UPS System or the batteries.