6-40

6.19 OPTIONAL ECC - EMERGENCY CIRCUIT CONVERTER – P/N 9100-1501

6.19.1 Installation

Indoor use only. Simple and fast installation in ceiling or wall mounted standard single gang E-box . Installation
must be performed by a qualified electrician per Installation, Operation and Maintenance Instructions, provided
with the ECC.

6.19.2 Operation

When used with an inverter system, the ECC is designed to allow you the ability to turn off ALL of the lighting in a
given area via the local switch, and still provide emergency lighting during a power failure. The device will provide
single phase power from the emergency source to the designated emergency fixtures regardless of their current
status (on or off), thereby insuring safe egress from the facility at all times. The automatic Diagnostic feature will
confirm the emergency system is ready to provide back up power.

6.19.3 Specification

Description:

ECC - EMERGENCY CIRCUIT CONVERTER OPTION

Part Number: 9100-1501-01 - 120 VAC

9100-1501-01- 277 VAC

Rating:

120 VAC - 20 A Ballast load, 1000 W Tungsten Lamp load, 20 A, 1 HP

277 VAC – 20 A Ballast load, 1800 W Tungsten Lamp load, 20 A, 1.5 HP

Operating Temperature: 20 to 150 F

Flame rating:

UL 94V-O

Size:

2.75”W x 4.75”H x 1.75”D (overall)

Low profile – recessed portion is only 1.5” deep

Color:

White

Weight:

8 oz.

EMERGENCY

POWER

UTILITY

POWER

TEST SWITCH

ILLUSTRATION 6-12: ECC EMERGENCY CIRCUIT CONVERTER