Online power, Input and output ampacity for various models – OnLine Power Protector 3 User Manual

Page 97

Advertising
background image

OnLine Power

D-1

APPENDIX D - Input and Output Ampacity for Various Models

Input and Output Ampacity for Various Models

SIZE

KVA/KW

INPUT

OUTPUT

OUTPUT

INPUT

AMPS

DC

I TOTAL

I R

VOLT

AMP

10KVA/8KW

208Y/120 208Y/120

27.8

22

31

192

56

480Y/277 480Y/277

12

10

14

192

56

480Y/277 208Y/120

28

22

14

192

56

15KVA/

12KW

208Y/120 208Y/120

42

33

47

192

84

480Y/277 480Y/277

18

15

21

192

84

480Y/277 208Y/120

42

33

21

192

84

20KVA/

16KW

208Y/120 208Y/120

56

45

62

192

112

480Y/277 480Y/277

24

19

27

192

112

480Y/277 208Y/120

56

45

27

192

112

25KVA/

20KW

208Y/120 208Y/120

69

56

77

288

85

480Y/277 480Y/277

30

24

35

288

85

480Y/277 208Y/120

69

56

35

288

85

30KVA/

24KW

208Y/120 208Y/120

83

67

93

288

102

480Y/277 480Y/277

36

29

41

288

102

480Y/277 208Y/120

83

67

41

288

102

40KVA/

32KW

208Y/120

208Y/120 111 89

123 312 169

480Y/277 480Y/277

48

39

54

312

169

480Y/277 208Y/120

111

89

54

312

169

50KVA/

40KW

208Y/120

208Y/120 139 111

155 552 120

480Y/277 480Y/277

60

48

67

552

120

480Y/277 208Y/120

139

111 67

552

120

62.5KVA/

50KW

208Y/120 208Y/120

174

139 194

552

-

480Y/277 480Y/277

75

60

84

552

-

480Y/277 208Y/120

174

139 194

552

-


Note: * I TOTAL: Total Amps, I R: Total Amp (Resistive load)