Online power, Appendix a - specifications, Specifications for kva, 0.8pf units – OnLine Power Protector 3 User Manual

Page 87

Advertising
background image

OnLine Power

A-1

APPENDIX A - SPECIFICATIONS

Specifications for KVA, 0.8pf Units

POWER RATING (KVA/KW)

10/8 15/12 20/16 25/20 30/24 40/32 50/40

62.5/50

INPUT and OUTPUT

INPUT VOLTAGE (VAC)

Three Phase, 4-Wire plus Ground, 208Y/120 or 480Y/277 VAC (-20% to +15%)

OUTPUT VOLTAGE (VAC)

Three Phase, 4-Wire plus Ground, 208Y/120 or 480Y/277 VAC

OUTPUT FREQUENCY (Hz)

60 Hz +0.5 Hz

VOLTAGE REGULATION

+/-3%, Regulated within CBEMA curve

OUTPUT WAVE FORM

Sine-Wave <5% THD.

EFFICIENCY

Minimum 90%

CREST FACTOR

3 to 1 Typical

SURGE PROTECTION

The UPS will protect itself and the load against surges as defined in ANSI/IEEE C62.41 Categories A and B.

ISOLATION

Complete from line. Output neutral bonded to ground

NOISE ISOLATION

-120 dB Common-Mode; -60 kB Transverse-Mode

BATTERY

Sealed maintenance-free (AGM) battery

RECHARGE CURRENT

Conforms to UL Standards

EXTERNAL BATTERY

Provisions for hardwire connection of optional external battery cabinets or DC source.

BATTERY

BATTERY RUN TIME

Consult OnLine Power

BATTERY TYPE

Sealed, Maintenance-Free, AGM, VRLA type

NOMINAL BATTERY VOLTAGE

192 VDC

192 VDC

192 VDC

288 VDC

288 VDC

312 VDC

552 VDC

552 VDC

OVERCURRENT PROTECTION

Circuit Breaker

PACKAGING

Batteries not housed in Same Enclosure as electronic (See Table 2-2)