Vav/cav controller configuration, Vav/cav confi guration screens, Vav/cav/mua operator interface sd – Orion System VAV II Controller v.1 User Manual

Page 25: 25 confi guration screens

Advertising
background image

VAV/CAV/MUA Operator Interface SD

VAV/CAV CONTROLLER CONFIGURATION

25

Confi guration Screens

In order to correctly set up the Unit Controller, you must fi rst confi gure
several parameters in regard to the type of HVAC unit and system you
have installed. Most of these values and operating parameters are only
set once at the initial system setup and are never changed.

Modular Service Tool Instructions

No matter what screen or menu you’re in, press

<CONFIGURATION>

.

The Unit Selection Screen will appear, shown below, requesting that you
enter the unit ID number.

Unit Selection*00*

Enter Unit ID#

Selected ID#: XXXX

Enter the correct unit ID number of the Unit Controller you want to
confi gure and then press

<ENTER>

. Once communication is established,

the *00* message will go away. Then

press

<

>

. You will then see

Unit Confi guration Screen #1. Press

<ENTER>

to save entered data

and

press

<

>

to scroll through the screens.

NOTE:

If the *00* remains, it indicates a communication failure

to the controller.

System Manager SD Instructions

From any Main screen, press

<SETPOINTS>

. The screen below will

appear because this option requires passcode clearance. Only a Level 2
passcode can change setpoints.

THIS ACTION REQUIRES

PASSCODE CLEARANCE

Enter Passcode: XXXX

If the correct passcode was entered, the Unit Selection Screen will be
displayed.

Unit Selection*00*

Enter Unit ID#

Selected ID#: XXXX

Enter the Unit ID of the controller you wish to change schedules for and
press

<ENTER>

. Once communication is established, the *00* message

will go away. Then

press

<

>

.

NOTE:

If the *00* remains, it indicates a communication
failure to the controller.

The following screen will be displayed:

Change Setpoints

Configure Unit

Save/Copy/Restore

Scroll down to the ‘Confi gure Unit’ option and press

<ENTER>

. This

will take you to the fi rst Confi guration Screen shown below.

Confi guration Screen #1 - Constant Volume

Mode Active

VAV/CAV Cnfg ID 0001

Constant Volume Mode

Active: No

Use < Or > To Change

This HVAC unit can be confi gured to operate as a Constant Volume or
VAV unit. The Constant Volume Mode does not provide Static Pressure
Control. You can install a Duct Pressure Sensor on a Constant Volume
unit and only monitor the Static Pressure. This is the only mode that
supports dehumidifi cation. Default is No.

Confi guration Screen #2 - Controlling Sensor

VAV/CAV Cnfg ID 0001

Controlling Sensor

SUPPLY AIR

Use < Or > To Change

The third line displays which sensor has been selected as the Controlling
Temperature for the VAV/CAV Controller. Default is SUPPLY AIR.

Available selections are as follows:

SUPPLY AIR

Supply Air Sensor

(Occupied Cooling with

Morning

Warmup)

OUTDOOR AIR

Outdoor

Air

Temperature

Sensor

(Occupied Cool, Heat & Vent)

SPACE TEMPERATURE

Space

Temperature

Sensor

(Occupied & Unoccupied

Cool, Heat & Vent)

RETURN AIR

Return Air Sensor (Occupied Cool,

Heat

&

Vent)

LOCAL ANALOG VALUE

Local

Analog

Value

VAV/CAV Confi guration Screens

Advertising