Vav/cav controller setpoints, Vav/cav setpoint screens, Vav/cav/mua operator interface sd 32 – Orion System VAV II Controller v.1 User Manual

Page 32

Advertising
background image

VAV/CAV CONTROLLER SETPOINTS

VAV/CAV/MUA Operator Interface SD

32

Description

Minimum

Default

Maximum

SAT Heating Spt

60ºF

140ºF

200ºF

Reset Limit Spt

60ºF

140ºF

200ºF

Setpoint Screen #6 - Heating/Cooling Supply

Control Use Deadband Of

VAV/CAV Spts ID 0001

Both Heating/Cooling

Supply Control Use

Deadband Of: 1ºF

All Heating and Cooling stages are staged up and down as the Supply
Air rises above or falls below the Supply Setpoint by an amount equal
to the number of stages divided into the Deadband Setpoint.

If you have 2 stages and a 1°F deadband, the staging begins at 0.5°F
above the setpoint for Stage 1 and 1°F above the setpoint for Stage 2.

Description

Minimum

Default

Maximum

Deadband Setpoint

0ºF

1ºF

20ºF

Setpoint Screen #7 - Morning Warm Up Setup

VAV/CAV Spts ID 0001

Morning WarmUp Setup

Target Temp: 72º F

Max Length.: 60 Min

If you need a Morning Warm-Up period on your HVAC unit, enter the
Target Temperature you want the Return Air Temperature to achieve and
the Max Length of time you want to spend in Warm-Up Mode trying to
achieve the Target Temperature. If you don’t need Morning Warm-Up,
simply ignore the Target Temperature Setpoint and enter a ‘0’ for the
Max Length value.

Description

Minimum

Default

Maximum

Target Temperature

50ºF

72ºF

90ºF

Max Length

0 Min

60 Min

240 Min

Setpoint Screen #8 - Outdoor Air Lockouts

VAV/CAV Spts ID 0001

Outdoor Air Lockouts

Cooling......: 50ºF
Heating......: 75ºF

The Unit Controller will Lockout Mechanical Heating or Cooling when
the Outdoor Air (OA) Temperature is above or below these setpoints.
On Heat Pump units, Compressor Cooling and Heating can only oper-
ate if the OA Temperature is above the Outdoor Air Cooling Lockouts.

Setpoint Screen #3 - HVAC Mode Select

Deadband

VAV/CAV Spts ID 0001

HVAC Mode Select

Deadband....: 1.0ºF

The HVAC Mode Select Deadband is the amount of error from setpoint
required to activate the Heating or Cooling Mode of operation.

This assumes the Return Air or Space Temperature are the controlling
sensors. If the Supply Air Temperature Sensor is the controlling sensor,
then this setpoint is not used.

Description

Minimum

Default

Maximum

HVAC Mode Select Deadband

0.1ºF

1.0ºF

10.0ºF

Setpoint Screen #4 - SAT Cooling Setpoint &

Reset Offset

VAV/CAV Spts ID 0001

Supply Air Setpoints

Cooling......: 55ºF
Reset Offset...: 0ºF

If no Reset of the Supply Air Temperature (SAT) Setpoint will be used,
then set the Cooling SAT Setpoint here, and leave the Reset Offset at 0.
If SAT Reset will be used, enter a Reset Offset value that will be added
to the Cooling Setpoint to create the upper limit for the Reset function.
Reset is always upward from the SAT Cooling Setpoint (lowest value) to
the SAT Cooling Setpoint plus Offset (highest value). This Cooling Reset
confi guration will be completed on Setpoint Screen #17 on page 34.

Description

Minimum

Default

Maximum

SAT Cooling Setpoint

40ºF

55ºF

70ºF

Cooling Reset Offset

0ºF

0ºF

20ºF

Setpoint Screen #5 - SAT Heating & Reset

Limit Setpoints

VAV/CAV Spts ID 0001

Supply Air Setpoints

Heating......: 140ºF
Reset Limit...: 140ºF

If no Reset of the Supply Air Temperature (SAT) Setpoint will be used,
then set the Heating SAT Setpoint here, and set the Reset Limit to the
same value. If SAT Reset will be used, set the Heating Setpoint as the
lowest Supply Air Setpoint Temperature desired, and set the Reset Limit
as the highest SAT desired. Reset is always upward from the Heating
Setpoint to the Reset Limit. This Heating Reset confi guration will be
completed on Setpoint Screen #18 on page 34.

VAV/CAV Setpoint Screens