Vav/cav controller setpoints, Vav/cav setpoint screens, Vav/cav/mua operator interface sd – Orion System VAV II Controller v.1 User Manual

Page 37

Advertising
background image

VAV/CAV/MUA Operator Interface SD

VAV/CAV CONTROLLER SETPOINTS

37

Confi guration Screen #28- #31 - Cool/Heat

Stage Delays

VAV/CAV Spts ID 0001

Cooling Stage Delays

Staging Up..: 3 Min
Staging Down: 1 Min

VAV/CAV Spts ID 0001

Cooling Stage Delays

Min Run Time..: 5 Min
Min Off Time..: 3 Min

VAV/CAV Spts ID 0001

Heating Stage Delays

Staging Up..: 3 Min
Staging Down: 1 Min

VAV/CAV Spts ID 0001

Heating Stage Delays

Min Run Time..: 5 Min
Min Off Time..: 1 Min

Both the Heating Stages and the DX Cooling Stages utilize Staging
Up and Down Delay Periods between stages and Minimum Run Times
and Off Times.

Both modes have their own set of Staging and Run Delay times. The
Heating timer screens look exactly the same as the Cooling except they
reference the Heating instead of Cooling.

See the VAV/CAV Controller Technical Guide for information on how
these Delays and Run Times are used.

Description

Minimum

Default

Maximum

Cooling Stage Up

3 Min

3 Min

15 Min

Cooling Stage Down

1 Min

1 Min

15 Min

Cooling Min Run Time

5 Min

5 Min

15 Min

Cooling Min Off Time

3 Min

3 Min

15 Min

Heating Stage Up

3 Min

3 Min

15 Min

Heating Stage Down

1 Min

1 Min

15 Min

Heating Min Run Time

2 Min

2 Min

15 Min

Heating Min Off Time

1 Min

1 Min

15 Min

Setpoint Screen #32 - Sensor Calibration for

SPC, SAT & RAT

Sensor Calibration

SPC: XX.Xº 0.00º
SAT: XX.Xº 0.00º
RAT: XX.Xº 0.00º

If the Space, Supply, or Return Air Temperature Sensors are reading
incorrectly, you can use this option to enter an offset temperature to
adjust the Sensor’s Temperature. Enter a positive Sensor Calibration
value to raise the Space Temperature Sensor, Supply Air Temperature
Sensor, or Return Air Temperature Sensor reading and a negative value
to lower the Sensor reading.

Description

Minimum

Default

Maximum

Sensor Calibration SPC

-100.0ºF

0.0ºF

+100.0ºF

Sensor Calibration SAT

-100.0ºF

0.0ºF

+100.0ºF

Sensor Calibration RAT

-100.0ºF

0.0ºF

+100.0ºF

Setpoint Screen #33 - Sensor Calibration for

OAT

Sensor Calibration

OAT: XX.Xº 0.00º

If the Outdoor Air Temperature Sensor is reading incorrectly, you can
use this option to enter an offset temperature to adjust the Sensor’s
Temperature. Enter a positive Sensor Calibration value to raise the
Outdoor Air Temperature Sensor reading and a negative value to lower
the Sensor reading.

Description

Minimum

Default

Maximum

Sensor Calibration OAT

-100.0ºF

0.0ºF

+100.0ºF

VAV/CAV Setpoint Screens