Minilink pd programming, Minilink pd confi guration screens, Vav/cav/mua operator interface sd 63 – Orion System VAV II Controller v.1 User Manual

Page 63: Minilink pd confi guration

Advertising
background image

MINILINK PD PROGRAMMING

VAV/CAV/MUA Operator Interface SD

63

MiniLink PD Confi guration Screens

MiniLink PD Confi guration

In order to correctly setup the MiniLink PD, you must fi rst confi gure sev-
eral parameters in regard to the type of system and operating parameters
for the system it is installed on. Most of these values and operating param-
eters are only set once at the initial system setup and are never changed.

Modular Service Tool Instructions

From any menu screen, press

<SETPOINTS>

. The Unit Selection Screen,

shown below, will appear requesting that you enter the unit ID number.

Unit Selection*00*

Enter Unit ID#

Selected ID#: XXXX

All MiniLink PDs are set at address 60. Enter the correct unit loop num-

ber for the loop the MiniLink Polling Device is connected to (for Loop 1
you would enter

<160>

) and press

<ENTER>

. Once communication is

established, the *00* message will go away. Then

press

<

>

.

NOTE:

If the *00* remains, it indicates a communication failure

to the controller.

You will then see Setpoint Screen #1. Press

<ENTER>

to save entered

data and

press

<

>

to scroll through the screens.

System Manager SD Instructions

From any Main screen, press

<SETPOINTS>

. The screen below will

appear because this option requires passcode clearance. Only a Level 2
passcode can change setpoints.

THIS ACTION REQUIRES

PASSCODE CLEARANCE

Enter Passcode: XXXX

If the correct passcode was entered, the Unit Selection Screen will be
displayed.

Unit Selection*00*

Enter Unit ID#

Selected ID#: XXXX

Enter the Unit ID of the controller you wish to change schedules for and
press

<ENTER>

. Once communication is established, the *00* message

will go away. Then

press

<

>

.

NOTE:

If the *00* remains, it indicates a communication
failure to the controller.

The following screen will be displayed:

Change Setpoints

Configure Unit

Save/Copy/Restore

Scroll to the ‘Change Setpoints’ option and press

<ENTER>

. This will

take you to the fi rst Setpoints Screen shown below.

Confi guration Screen #1 - System Type

Polling Unit Config

System Type

Selection: ZONING

Use < Or > To Change

Select VAV or ZONING. This screen allows you to select whether you
want the system to behave as a VAV system or a Zoning System. If you
select VAV, this will allow tenant logging for your VAV system.

Confi guration Screen #2 - Last Polled Zone

Polling Unit Config

Last Polled Zone

Address: XX

[Enter Last Zone]

This zone is the last zone on the local loop of your zoning system that is
to be included in zone voting. Valid entry is 1 to 25.

Confi guration Screen #3 - Mode Changeover

Time

Polling Unit Config

Mode Changeover Time

Minutes: XX

[Enter Period Time]

This is the amount of time that you want to allow between changeover
from heating to cooling modes. Valid entry is 5 to 60 minutes.