MUA II CONTROLLER CONFIGURATION

VAV/CAV/MUA Operator Interface SD

42

MUA II Confi guration Screen Index

MUA II Confi guration Screen Index

The available Confi guration Screens for the MUA II Controller are
listed on the next few pages by sequential screen number. When the
Unit Controller is confi gured for the fi rst time, it is best to start with
screen #1 and proceed to each screen in numerical order until you have
viewed all available Confi guration Screens. This ensures that you have
seen all the available Controller confi guration possibilities and have the
opportunity to change or accept the defaults for each screen.

Once the unit is confi gured and you decide to change one of the screen
options, it is helpful to know what screen number contains the confi gu-
ration you wish to change. With this in mind, the following is a list of
all the MUA II Confi guration Screens in numerical order with a brief
listing of the confi guration feature available on each screen.

Screen #1

Proof of Flow Switch Installed

Screen #2

OA Humidity Sensor Installed

Screen #3

Heat in Dehumidify Installed

Screen #4

If External Heat, Output Range

Screen #5

Is External Heat Reverse Action

Screen

#6

Broadcast

Outside

Temperature

Screen #7

Broadcast Humidity Reading

Screens #8-27

Relay Confi guration Relays 2-21

Modular Service Tool Instructions

No matter what screen or menu you’re in, press

<CONFIGURATION>

.

The Unit Selection Screen will appear, shown below, requesting that you
enter the unit ID number.

Unit Selection*00*

Enter Unit ID#

Selected ID#: XXXX

Enter the correct unit ID number of the Unit Controller you want to
confi gure and then press

<ENTER>

. Once communication is established,

the *00* message will go away. Then

press

<

>

. You will then see

Unit Confi guration Screen #1. Press

<ENTER>

to save entered data

and

press

<

>

to scroll through the screens.

NOTE:

If the *00* remains, it indicates a communication failure

to the controller.

System Manager SD Instructions

From any Main screen, press

<SETPOINTS>

. The screen below will

appear because this option requires passcode clearance. Only a Level 2
passcode can change setpoints.

THIS ACTION REQUIRES

PASSCODE CLEARANCE

Enter Passcode: XXXX

If the correct passcode was entered, the Unit Selection Screen will be
displayed.

Unit Selection*00*

Enter Unit ID#

Selected ID#: XXXX

Enter the Unit ID of the controller you wish to change schedules for and
press

<ENTER>

. Once communication is established, the *00* message

will go away. Then

press

<

>

.

NOTE:

If the *00* remains, it indicates a communication
failure to the controller.

The following screen will be displayed:

Change Setpoints

Configure Unit

Save/Copy/Restore

Scroll down to the ‘Confi gure Unit’ option and press

<ENTER>

. This

will take you to the fi rst Confi guration Screen shown below.