Mua ii controller setpoints, Mua ii setpoint screen index, Vav/cav/mua operator interface sd – Orion System VAV II Controller v.1 User Manual

Page 45: Setpoints - general procedures, Setpoint screen index

Advertising
background image

VAV/CAV/MUA Operator Interface SD

MUA II CONTROLLER SETPOINTS

45

MUA II Setpoint Screen Index

Setpoints - General Procedures

Modular Service Tool Instructions

From any menu screen, press

<SETPOINTS>

. The Unit Selection

Screen, shown below, will appear requesting that you enter the unit
ID number.

Unit Selection*00*

Enter Unit ID#

Selected ID#: XXXX

Enter the correct unit ID number of the Unit Controller you want to
change Setpoints for and press

<ENTER>

. Once communication is

established, the *00* message will go away. Then

press

<

>

. You will

then see Setpoint Screen #1. Press

<ENTER>

to save entered data and

press

<

>

to scroll through the screens.

NOTE:

If the *00* remains, it indicates a communication failure

to the controller.

System Manager SD Instructions

From any Main screen, press

<SETPOINTS>

. The screen below will

appear because this option requires passcode clearance. Only a Level 2
passcode can change setpoints.

THIS ACTION REQUIRES

PASSCODE CLEARANCE

Enter Passcode: XXXX

If the correct passcode was entered, the Unit Selection Screen will be
displayed.

Unit Selection*00*

Enter Unit ID#

Selected ID#: XXXX

Enter the Unit ID of the controller you wish to change schedules for and
press

<ENTER>

. Once communication is established, the *00* message

will go away. Then

press

<

>

.

NOTE:

If the *00* remains, it indicates a communication
failure to the controller.

The following screen will be displayed:

Change Setpoints

Configure Unit

Save/Copy/Restore

Scroll to the ‘Change Setpoints’ option and press

<ENTER>

. This will

take you to the fi rst Setpoints Screen shown below.

Setpoint Screen Index

The available Setpoint Screens for the MUA II Controller are listed on
the next few pages by sequential screen number. When each MUA II
Controller is confi gured for the fi rst time, it is best to start with screen #1
and proceed to each Setpoint Screen in numerical order until you have
viewed all available Setpoint Screens. This ensures that you have seen
all of the available MUA II Controller Setpoint possibilities and have
the opportunity to change or accept the defaults for each screen. Once
the unit Setpoints are confi gured and you decide to change one of the
screen options, it is helpful to know what screen number contains the
confi guration you wish to change. With this in mind, the following is a
list of all the MUA II Setpoint Screens in numerical order with a brief
listing of the Setpoint feature available on each screen:

Screen #1

Supply Air Temperature Setpoint

Screen #2

Staging Deadbands—Cooling & Heating

Screen #3

Unoccupied Deadbands—Cooling & Heating

Screen #4

Systems with Re-Heat—Dewpoint Control

Setpoint

Screen #5

Enthalpy Staging—Deadband & Hysterisis

Screen #6

Heat Delay During Dehumidifi cation Will Occur

Screen #7

Alarm Limits—High & Low Supply Air

Temperature

Screen #8

Supply Air Alarms If Out of Range For

Screen #9

Set Supply Air Temperature Reset

Screen #10

Set Dewpoint Reset

Screen #11

Cooling Stage Delays—Staging Up & Down

Screen #12

Cooling Stage Delays—Min Run & Off Times

Screen #13

Heating Stage Delays—Staging Up & Down

Screen #14

Heatng Stage Delays—Min Run & Off Times

Screen #15

External Modulating Heat—Deadband & Time

Period

Screen #16

Push-Button Override Duration

Screen #17

Slide Offset Duration

Screen #18

HVAC Schedule

Screen #19

Fan Time Delay Before Activation Can Occur

Screen #20

Sensor Calibrations For SAT & OAT

Screen #21

Sensor Calibration Reset Sensor - Space

Advertising