VAV/CAV/MUA Operator Interface SD

VAV/CAV CONTROLLER SETPOINTS

33

If the Outdoor Air Temperature drops below the Cooling Lockout set-
point by 1°F, the DX cooling will be locked out until the Outdoor Air
Temperature rises 1°F back above the Lockout Setpoint. The same 1°F
deadband applies to the Heat Lockout Setpoint except the Outdoor Air
locks out the Heating when it is above the lockout instead of below the
lockout.

Description

Minimum

Default

Maximum

OA Lockouts Cooling

-30ºF

50ºF

80ºF

OA Lockouts Heating

50ºF

75ºF

90ºF

Setpoint Screen #9 - Low Cutoff Temperature

VAV/CAV Spts ID 0001
All Cooling Cuts Off

If Supply Air Temp
Drops Below: 40ºF

If the Supply Fan VFD drops below this value, the Heat will stage off.
The Supply Fan VFD will not be allowed to drop below this value
while the unit is in Heating Mode unless the static pressure rises 0.5”
above the static setpoint See the VAV/CAV Controller Technical Guide
for detailed information on the Low Supply Air Temperature Cutoff
sequence of operation.

Description

Minimum

Default

Maximum

Lo SAT Cutoff

30ºF

40ºF

60ºF

Setpoint Screen #10 - High Cutoff

Temperature

VAV/CAV Spts ID 0001
All Heating Cuts Off

If Supply Air Temp
Exceeds: 170ºF

If the Supply Air Temperature ever exceeds this value, all Heating
stages are immediately cutoff, regardless of run time. See the VAV/CAV
Controller Technical Guide
for detailed information on the High Supply
Air Temperature Cutoff sequence of operation.

Description

Minimum

Default

Maximum

Hi SAT Cutoff

60ºF

170ºF

250ºF

VAV/CAV Setpoint Screens

Setpoint Screen #11 - Supply Fan VFD

Percentage

VAV/CAV Spts ID 0001

Heating Stages Off
If Supply Fan VFD Is
Below: 30%

If the Supply Fan VFD drops below this value, the Heat will stage off.
The Supply Fan VFD will not be allowed to drop below this value while
the unit is in Heating Mode unless the Static Pressure rises 0.5” above
the Static Setpoint.

Description

Minimum

Default

Maximum

Below Setpoint

0%

30%

100%

Setpoint Screen #12 - Low Ambient Protection

VAV/CAV Spts ID 0001

Pre-Heat Output ON
Continuous Below
OAT Level: 0ºF

If your air handler has at least one Heating stage and you require a Low
Ambient Protection or Preheating of the air stream, you can enter a Sup-
ply Air Temperature value that causes one stage of Heating to come on
and remain on continuous if the Outdoor Air Temperature drops below
this level. If you don’t want this protection, do not confi gure any relays
for this function.

Description

Minimum

Default

Maximum

Low Ambient Level

-50ºF

0ºF

70ºF

Setpoint Screen #13 - Economizer OAT/WB

Enable

VAV/CAV Spts ID 0001

Economizer Setpoints

OAT/WB Enable: 55ºF

If an Outdoor Air Humidity Sensor is not connected to the Unit Con-
troller and the Outdoor Air Temperature falls below this Setpoint, the
Economizer can be used for Free Cooling. If an Outdoor Air Humidity
Sensor is connected to the controller, then a Wetbulb Temperature will
be calculated and used instead of the Outdoor Air Drybulb Temperature
to determine when Free Cooling can be used.

Description

Minimum

Default

Maximum

Economizer Setpoints

OAT/WB Enable

-30ºF

55ºF

80ºF