Zone

Zone

SYSTEM CONNECTION

VAV/CAV/MUA Operator Interface SD

8

Power/Comm Board Wiring

Figure 5: Typical Power/Comm Board Wiring

A Power/Comm

Of

Using

. You Can Also Use

Another Power/Comm

Board, A System Manager Or A VAV/Zone
Controller.

Cable Can Be Used To

Connect With The MiniLink PD Instead

2 Conductor Twisted Pair With Shield

Cable

A Power/Comm

Cable To Connect With

Power/Comm Cable To

Power/Comm

System Manager, Or VAV/Zone Controllers On Local Loop Only.

Other

Board(s),

If Desired, Instead Of Using A
Power/Comm Cable, You Can Use 2
Conductor Twisted Pair With Shield
Cable To Connect To The Power/
Comm Board From The Unit
Controller, MiniLink PD, Or Another
Power/Comm Board.

Line Voltage

24VAC

R

SH

T

R

SH

T

R

SH

T

R

SH

T

All Comm Loop Wiring Is

Straight Thru

Local Loop RS-485

9600 Baud

Local Loop RS-485

9600 Baud

24VAC Transformer (By Others)

4 Amp Slow Blow Fuse

WARNING!

DO NOT GROUND THE 24V TRANSFORMER
THAT IS TO BE USED WITH THE POWER/COMM
BOARDS. GROUNDING OF THE TRANSFORMER
WILL DAMAGE THE POWER/COMM BOARD
AND ALL BOARDS CONNECTED TO IT. A
SEPARATE TRANSFORMER MUST BE USED
FOR EACH POWER/COMM BOARD. NO
EXCEPTIONS. DO NOT CONNECT ANY OTHER
DEVICES TO THE TRANSFORMER USED FOR
THE POWER/COMM BOARD!

NOTE:
Diagram Shown Is For Wiring Of
Power/Comm Board When Used
For Connecting Local Loop Devices
Such As VAV/Zone Controllers,
System Manager(s) and Other
Power/Comm Boards.