Vav/cav controller setpoints, Vav/cav setpoint screens, Vav/cav/mua operator interface sd – Orion System VAV II Controller v.1 User Manual

Page 35

Advertising
background image

VAV/CAV/MUA Operator Interface SD

VAV/CAV CONTROLLER SETPOINTS

35

Setpoint Screen #21 - HVAC Schedule

VAV/CAV Spts ID 0001

AHU Schedule By
Schedule Number: 0
0=AHU 1-7=Scheduler


Normally, the AHU will use its own internal time clock and week
schedules to set the Occupied Mode of operation. If you have several
air handlers, you can connect an external scheduling device to the com-
munications loop and program the air handler for the desired schedule to
follow. If the AHU is using its internal schedule, enter

<0>

for Internal.

Description

Minimum

Default

Maximum

Schedule Number

0

0

1 to 7

Setpoint Screen #22 - Economizer Maximum

Position if High CO

2

Level

VAV/CAV Spts ID 0001

Maximum Economizer

Position if High CO2
Level Occurs.: 100%

If you have confi gured the air handler to read a CO

2

Sensor, it will over-

ride the Minimum Economizer Position up to this position if the CO

2

level rises above its setpoint by the adjustable Reset Range amount. See
Setpoint Screen #23
.

NOTE:

The Minimum Position is determined by the user-

adjustable Min Position Setpoint on Setpoint Screen #14
on page 34.

Description

Minimum

Default

Maximum

Maximum Economizer

Position If High CO

2

Level Occurs

Economizer

Minimum

Position

100%

100%

Setpoint Screen #23 - CO

2

Protection Limit

VAV/CAV Spts ID 0001
CO2 Protection Limit

Max Level: 900 PPM
Reset Range: 100 PPM

If you confi gure the air handler to read a CO

2

Sensor, the Max Level is the

point at which the Economizer Minimum Position starts to reset upward.
As the CO

2

level rises above the Max Level by the Reset Range amount,

the Economizer will have reset its Minimum Position proportionally up
to the previously defi ned Economizer Maximum Position in High CO

2

.

Description

Minimum

Default

Maximum

CO

2

Protection Limit

Max Level

0 PPM

900 PPM

5000 PPM

CO

2

Protection Limit
Reset Range

0 PPM

100 PPM

1000 PPM

VAV/CAV Setpoint Screens

VFD Percentage Cool Reset Example:
Hi Reset = 70%

SAT Setpoint (Spt) = 55°F

Lo Reset = 30%

SAT Setpoint (Rst) = 65°F

VFD Percentage Heat Reset Example:

Hi Reset = 30%

SAT Setpoint (Spt) = 90°F

Lo Reset = 70%

SAT Setpoint (Rst) = 120°F

Input Voltage Cool Reset Example:

Hi Reset = 0 Volts

SAT Setpoint (Spt) = 55°F

Lo Reset = 10 Volts

SAT Setpoint (Rst) = 65°F

Input Voltage Heat Reset Example:

Hi Reset = 0 Volts

SAT Setpoint (Spt) = 90°F

Lo Reset = 10 Volts

SAT Setpoint (Rst) = 120°F

Setpoint Screen #19 - Supply Fan Starting

Delay Timer

VAV/CAV Spts ID 0001

Start Fan Delay

Timer...: 999s

[999= Unit Addr x 5]

This is the amount of time that the main HVAC unit fan will delay before
starting after an occupied signal is initiated or after a power failure. The
default value is 999. With the default value, the delay will be equal to
the unit address multiplied by 5.

Example: Controller ID (address) 18 would cause a 90 second delay
when the default value of 999 is used. Controller ID (address) 30 would
cause a 150 second delay when the default value of 999 is used.

Description

Minimum

Default

Maximum

Fan Start Delay Timer

0 Sec

999 Sec

999 Sec

Setpoint Screen #20 - Mechanical Heat/Cool

Failure Time Period

VAV/CAV Spts ID 0001
Mechanical Heat/Cool

Failures Occur After
No Change In 15Min

When Heating or Cooling Mode is initiated and staging is activated, if the
Supply Air Temperature does not rise or fall 5°F within the Mechanical
Heat/Cool Failures Occur After No Change In Setpoint time period, a
Mechanical Heating or Cooling Failure Alarm will be generated. The
alarm is for status reporting only. The HVAC unit will continue to run.

Description

Minimum

Default

Maximum

Mechanical Heat/Cool

Failures Occur After

No Change In

0 Min

15 Min

300 Min

Advertising