Mua ii controller setpoints, Mua ii setpoint screens, Vav/cav/mua operator interface sd – Orion System VAV II Controller v.1 User Manual

Page 47

Advertising
background image

VAV/CAV/MUA Operator Interface SD

MUA II CONTROLLER SETPOINTS

47

Setpoint Screen #9 - Set Supply Air

Temperature Reset

MUA II SPTS 0001

Set SAT Temp Reset

SPC = 0 Spt = 70
SPC = 0 Rst = 70

A Type III Thermistor Sensor connected to Analog Input #1 can be used

to reset the Supply Air Temperature. This screen allows you to set the
Reset Source Temperatures that the Reset will begin at and the new Reset
Supply Air Temperature range. Determine a desired Space Temperature
you would like to maintain and enter a temperature in the top SPC fi eld
that is 2 degrees higher than your desired Space Temperature. Next,
using the desired Space Temperature you would like to maintain, enter
a temperature in the bottom SPC fi eld that is 2 degrees lower than your
desired Space Temperature. Then enter a value in the “Rst” fi eld on
this screen that is equal to the highest Supply Air Temperature desired.
Whatever Supply Air Temperature you enter for “Rst”, when added
together and divided by 2, should result in a temperature value equal to
your desired Space Temperature.

The “Spt” fi eld value cannot be changed from this screen. This Supply
Air Temperature Setpoint (Spt) must be set from Setpoint Screen #1 on
page 46 and should be set to the lowest Supply Air Temperature that
is desired.

Supply Air Temperature Reset Example:
*Desired Space Temperature is 70°F

Space Temperature (SPC) = 72°F SAT Setpoint (Spt) = 55°F
Space Temperature (SPC) = 68°F SAT Setpoint (Rst) = 85°F

Description

Minimum

Default

Maximum

Minimum Range

40ºF

0ºF

100ºF

Maximum Range

40ºF

0ºF

100ºF

Reset

SAT Spt

SAT Spt

Spt + 50ºF

MUA II Setpoint Screens

Setpoint Screen #7 - Alarm Limits

MUA II SPTS 0001

Alarm Limits

Hi SAT Limit: 150ºF
Lo SAT Limit: 0ºF

If the Supply Air Temperature ever rises above the High SAT Limit or
drops below the Low SAT Limit for a user-defi ned period of time, an
alarm is generated.

Description

Minimum

Default

Maximum

High SAT Limit

50ºF

150ºF

150ºF

Low SAT Limit

0ºF

0ºF

70ºF

Setpoint Screen #8 - Supply Air Alarm

MUA II SPTS 0001
Supply Air Alarms If

Out Of Range For

30 Min

This is the amount of time the Supply Air Temperature must be outside
either the High or Low SAT Limit Setpoint before it generates an alarm.

Description

Minimum

Default

Maximum

Supply Air Alarms If

Out of Range For X

Minutes

0 Min

30 Min

300 Min