Vav/zone controller programming, Vav/zone confi guration screens – Orion System VAV II Controller v.1 User Manual

Page 55

Advertising
background image

VAV/ZONE CONTROLLER PROGRAMMING

VAV/CAV/MUA Operator Interface SD

55

VAV/Zone Confi guration Screens

Confi guration Screen #10 - Dump Zone

XX Box Cnfg IDXXXX

Is This A Dump Zone

(No Actuator): NO

Use < Or > To Change

A “Dump Zone” is used when you want to control a duct heater or
baseboard heater independently. A VAV/Zone Controller board with a
relay expansion board is used for this purpose. No damper or actuator
is used. If you need to control an auxiliary heater, select YES; otherwise,
select NO.

Confi guration Screen #11 - HVAC Unit is on

Separate Loop

XX Box Cnfg IDXXXX

HVAC Unit is on

Separate Loop: NO

Use < Or > To Change

If this system has 1 HVAC unit controlling boxes on multiple loops
and the HVAC unit is on a different loop than this box, select YES;
otherwise, select NO.

Advertising