Mua ii controller status, Mua ii status screens, Vav/cav/mua operator interface sd 52 – Orion System VAV II Controller v.1 User Manual

Page 52

Advertising
background image

Zone

Zone

MUA II CONTROLLER STATUS

VAV/CAV/MUA Operator Interface SD

52

MUA II Status Screens

Status Screen 6 - Current Reset Temperature

& Humidity Reading

MUA-II v.2.01 0001

Space Temp: XX.XºF
Reset RH..: XX.X%

Line 2

Current Reset Temperature Reading

Line 3

Current Reset Humidity Reading

Status Screen 7 - MODGAS Output %, MHGRV

Output % & External Heat Output %

MUA-II v.2.01 0001

MODGAS Pos..: XXX%
MHGRV Pos...: XXX%
External Heat: 0.0%

Line 2

Current MODGAS Heating Output Signal

Indicates the percentage of the output signal being supplied
to the MODGAS Controller when you have one connected
to your HVAC unit. If you do not have a MODGAS
Controller connected to your

Unit Controller

, this screen

will indicate [NO MODGAS DETECTED].

Line 3 Current MHGRV Reheat Valve Output Signal
Percentage

Indicates the percentage of the output signal being supplied

to the MHGRV Controller when you have one connected

to

your

Unit Controller

.

If you do not have an MHGRV

Controller connected to your Unit Controller, this screen

will indicate [NO REHEAT DETECTED].

Line 4 External Heat Signal

This is the signal, 0-10 or 2-10 VDC, to an optional external

modulating

heating

device.

Status Screens 8-28 - Relays

VAV/CAV v 1.00 0001

On Board Rly 1

FAN

Off

Line 2 Relay Status

On Board Relays 1-5, Expansion Board Relays 1-16.

On Board Relay #1 is the Fan and is not confi gurable.

Line 3 Relay description of what it is confi gured for

Possible options are as follows:

Not

Used

Gas

Re-Heat

Heat

Stage Exhaust

Fan

Cool

Stage Pre-Heater

Warm-Up

Mode

External

Heat

Rev

Valve

Line 4 Current relay status On or Off or FRC

FRC indicates the relay is forced to its current condition.

Status Screens 29-31 - Alarm Conditions

VAV/CAV v 1.00 0001

NO ALARMS!

VAV/CAV v 1.00 0001

ALARMS PRESENT

SCROLL DOWN TO VIEW

Line 2 Blank

Line 3 NO ALARMS! OR ALARMS PRESENT

If alarms are present, the screens that follow will display

one or more of the following:

No Supply Temp Fan Proving

No

Outdoor

Temp

Low

SAT

No Outdoor RH High SAT

Press

<

>

to scroll through all active alarms.

For

Alarm

Defi nitions, see the MUA II Controller

Technical

Guide.