Space Ray LTS Series Two Stage User Manual

Page 51

Advertising
background image

Form #43155040

-50-

May 2013

Call for heat ends and the heater shut

s of

f?

Y

es

No

Troubleshooting ends.

Thermost

at is not

working properly

.

Replace it if necessary

.

Is the green light still on?

Y

es

No

T

urn of

f gas &

electricity immediately

.

Replace the gas valve.

Remove valve lead at ignition module. Does valve close?

No

Y

es

Recheck thermost

at

and wiring.

T

roubleshooting

continued from the previous p

age.

Replace the relay

.

Check the wire connecting relay terminal 4 and terminal L1 for continuity

.

Replace if no continuity

.

Correct connection.

Replace transformer

.

Correct Connection.

Rest

art

troubleshooting.

Check the thermost

at

for continuity

. Replace

if no continuity

.

Is there 24V between terminals 1 and 5 on the relay?

Y

es

No

Are transformer’

s two

lead wires securely connected to L1 and L2, respectively?

Is there 24V between transformer terminals on the secondary side?

No

Y

es

Is the red wire connecting relay terminal 5 and terminal LO of round terminal block securely?

No

Y

es

T

roubleshooting

continued from the previous p

age.

Is the black wire connecting one transformer terminal and terminal C of round terminal block securely?

No

Y

es

Is the white wire connecting the other transformer terminal and relay terminal 1 securely?

No

Y

es

Is there 24 V between terminals LO and C on the round terminal?

No

Y

es

Correct connection.

Correct connection.

Correct connection.

No

Y

es

Is the black wire connecting terminal L1 and relay terminal 4 securely?

No

Y

es

Is there 120 V between relay terminal 4 and ground?

No

Y

es

1

Advertising