Super Systems 9210 Series User Manual

Page 32

Advertising
background image

M4557 - Model 9210 Nitriding Controller

SSi Manual SERIES 9210-M4557-Nitriding

Page 32 of 32

IP Address Mask 3

255

IP Address Mask 4

0

IP Address Gateway 1

192

IP Address Gateway 2

168

IP Address Gateway 3

1

IP Address Gateway 4

1

Highlighting the parameter that needs to be entered and pressing the Enter button displays a numeric

keypad that can be used to enter the required value. This will range from 0 to 256.

The default IP address is: 192.168.0.200
The default IP Address Gateway is: 192.168.1.1

Pressing the Esc key returns you to the configuration menu.

Event Control

This menu option will allow the user to set up the

event control for the 9210. The “Hold Instrument
Number” selection will display a numeric keypad

that can range from 0 to 11. The “Hold Minimum

PV” selection will display a numeric keypad that

will range from 0 to 4000. The “Hold Maximum

PV” selection will display a numeric keypad that

will range from 0 to 4000. The “Event for
Program Run” selection will display a numeric

keypad that will range from –1 to 15. A value of

1 means there is no event. The “Event for

Program Reset” selection will display a numeric

keypad that will range from –1 to 15. A value of

1 means there is no event. The “Event 0” through
“Event 15” selection will allow the user to assign

the specific events. The list of options for this

selection is:

Event Inactive

Event Active, Open Triggers Hold

Event Active, Closed Triggers Hold

Valve Configuration


This screen provides setup information for the 9210

on the flow controller boards.

The “Decimal Place” selection determines how the

9210 will display gas flows. This will display a

numeric keypad that can range from 0 to 4.

The “Valve Control Mode” selection determines how
the 9210 will adjust gas flows if required for

%Dissociation. This will display a screen that will

allow the user to select the mode. The choices are:

• Individual Trim

• Flow

• Ratio

• Auto

The “D.A. Switch Point” selection determines the

control switch point for switching the atmosphere display from %Dissociation to Kn. This will display a