background image

M4557 - Model 9210 Nitriding Controller

SSi Manual SERIES 9210-M4557-Nitriding

Page 6 of 6

About This Manual

This instrument is designed for Nitriding control and configured per individual customer requirements. This
manual covers the operation of the Model 9210 Nitriding Controller, the Nitriding Control System and the

Gas Flow Panel.

Controller Description

The Model 9210-Nitriding instrument is a multi-loop Proportional Integral Derivative (PID) controller that
can be custom configured to control up to three Nitriding process loops. General features of this product

include:

The Model 9210 is powered by 24 VDC,

NOT

LINE Voltage. Please be careful when connecting power to

this controller. Connecting anything other then 24 VDC will cause serious damage.


Approximate Box Dimensions

2.75" x 4" x 4.5"

Power Requirements

24VDC, 4 Watts

Digital Output Rating

300VAC / 1 AMP

Analog Output Load Rating

1000 Ohms (Total)

Controller Enclosure Rating

IP10 – hand protected

Number of RS232 Ports

Two (2)

Number of Ethernet Ports

One (1)

Number of RS485 Host Ports

One (1)

Number of RS485 Slave Ports

Two (2)

Number of Internal Relays

Eight (8)

Number of Analog Inputs

Three (3)

Number of Analog Outputs

Two (2)

Number of Digital Inputs

Four (4)

Number of Control Loops

Three (3)


The control enclosure is powered by 120 VAC, Single Phase, 60 Hz (Line Power). Line voltage for the

isolation relays comes from the same source.


!