2.0 SPECIFICATION

2.1

Enclosure - NA

2.2 Dimensions

Electronics unit: H. 180mm W.85mm D.60mm See figure 1

.

2.3 Ambient

Temperature

Sensor unit: -10…50°C Max

2.4

Display - NA

2.4

Analog outputs – isolated (Optional)

4…20mAV proportional to 0..100% Hydrogen (minimum load 500 ohm.) Optional

2.5

Alarm indicators (Optional)

Voltage free contacts SPDT Relay 1A /120Vac or 2A /240Vac

High alarm 1 relay (Set to 0.6% Hydrogen)

High alarm 2 relay (Set to 1.0% Hydrogen)

2.6 Communications

RS232

Set up: 9600 Baud, 1 start bit, 8 data bits, 1 stop bit, no parity, hardware (CTS/RTS) handshaking.
See Appendix 1 for proposed communication protocol.

DTE male 9w

PIN

NAME

3

TX(out)

2

RX (in)

7

RTS (out)

8

CTS (in)

5

GND

RS485

Optional