M4557 - Model 9210 Nitriding Controller

SSi Manual SERIES 9210-M4557-Nitriding

Page 44 of 44

values are within the deviation limit band. If the temperature falls outside of the band, the ramp

will wait until the temperature is within the band.

GZRAMP

This is a

Guaranteed Ramp

opcode for a zone. The process value must be within the deviation

band to allow the ramp timer to run. The temperature data is the temperature set point, the

atmosphere data is the atmosphere setpoint, and the option data is the ramp time in hours and

minutes. The band limit can be changed by the

SET_WAIT

opcode.

GZ_SOAK

This is a

Guaranteed Soak

opcode for a zone. The temperature process value must be within the

deviation band to allow the soak timer to run. The option value is the soak time in hours and

minutes. The band limit can be changed by the

SET_WAIT

opcode.

HIGH_AL

This opcode is used to enable a high limit alarm on the temperature process and/or the

atmosphere process. The temperature data is the high limit point for the temperature process.

The atmosphere data is the high limit point for the atmosphere process. This alarm remains active
until the program ends.

HIGH_PO

This opcode is used to enable a high limit alarm on the temperature percent output and/or the

atmosphere percent output. The temperature data is the high limit point for the temperature

percent output. The atmosphere data is the high limit point for the atmosphere percent output.

This alarm remains active until the program ends.

ID_SET

This opcode is used to set the ID number to the value specified in the temperature data. The

atmosphere and option data are not used. The ID number is provided as a feature to track loads

or jobs and is not used by any controller.

ID_INC

This opcode increments the ID number by one. No data is required.

ID_INQ

This opcode is used to compare the ID value to the value in the temperature data. The option

data is equal, high, or low. The

LIMIT

opcode immediately following this opcode sets a time limit

on the wait. A

BRANCH

opcode immediately following this opcode can be used to change the

program flow based on the inquiry results.

IN_inq

The

Input Inquiry

opcode will allow the user to check one of the inputs for a specific value. The

temperature data is the value to check for. The atmosphere data is the input to check. The

options are wait, wait up, or wait down.

The

LIMIT

opcode immediately following this opcode sets a time limit on the wait.

A

BRANCH

opcode immediately following this opcode can be used to change the program flow

based on the inquiry results.

JUMP

The

JUMP

opcode is used to go to another program when no return is needed. The option data is

the program number to execute next. This differs from the

GOSUB

opcode in that the

JUMP

will

not return to the calling recipe when the next recipe has finished.

LIMIT

This option is used to place a time limit on a wait or inquiry step. The option data is the time limit

to wait in hours and minutes. Should the time run out before the wait or inquiry is satisfied an

alarm occurs.

LOW_AL

This opcode is used to enable a low limit alarm on the temperature process and/or the

atmosphere process. The temperature data is the low limit point for the temperature process. The
atmosphere data is the low limit point for the atmosphere process. This alarm remains active until

the program ends.