M4557 - Model 9210 Nitriding Controller

SSi Manual SERIES 9210-M4557-Nitriding

Page 47 of 47

The default band can be set under the configuration menu and is typically 15degrees. The band

limit can be changed by the S

ET_WAIT

opcode.

The

LIMIT

opcode immediately following this opcode sets a time limit on the wait.

A

BRANCH

opcode immediately following this opcode can be used to change the program flow

based on the inquiry results.

TOD_INQ

This opcode is a time of day inquiry which would be used to start a process or subroutine at a

specific hour and minute. The option data is entered in the 24 hour format (i.e. 2:30pm is 14:30).

TZ_INQ

The zone temperature inquiry is used to wait for the actual control zone temperature to reach the

value specified in the Temperature data.

The options are:

• wait, reach within band

• wait up, reach or exceed the set point

• wait down, reach or be less than the set point

The default band can be set under the

Configuration

Menu and is typically 15 degrees. The band

limit can be changed by the S

ET_WAIT

opcode.

The

LIMIT

opcode immediately following this opcode sets a time limit on the wait. A

BRANCH

opcode immediately following this opcode can be used to change the program flow based on the

inquiry results.

VALVE SETPOINT

This opcode is used to set the flow rate of gas for each valve. The temperature data is

the Setpoint Value. The atmosphere data is the Trim Range. The option data is the valve.

ZONE_OFF

The

Zone Offset

opcode is used to set an offset to be added to the set point sent to a specific

zone. Either temperature, atmosphere, or both can be offset. The same loop (furnace) can have

different offsets for each zone. The zones must be defined in the zone configuration.

For example, a pit furnace has three zones: top, middle, and bottom.

The zones could be defined as:

top = zone 1,

middle = zone 2 ,

bottom = zone 3.

If the

ZONE_OFF

opcode is used in a program with temperature data = 50 and zone = 1, then a

temperature set point value in the following steps of 1700 would be sent to the middle and bottom

as 1700 and the top as 1750.

Z_SETPT

This opcode is used to set the temperature and/or atmosphere set points for a zone. Either or

both of the set points can be specified. The options are None, Wait, Wait Up, or Wait Down. If

both set points are specified, the Wait applies to both.