M4557 - Model 9210 Nitriding Controller

SSi Manual SERIES 9210-M4557-Nitriding

Page 42 of 42

Chapter 5 - SERIES 9210 Opcodes


Programmer Description

The SERIES 9210 series Atmosphere/Temperature Recipe Programmer provides a convenient

operator interface and recipe programmer.

The programmer uses enhanced Opcodes that reduce the number of steps required for a program.
Each step consists of an opcode, an optional temperature value, an optional atmosphere value, and

an option value. The opcode determines how and if each of the three values are used.

Opcodes

NO-OP

This no operation code does nothing and is used as a place hold on programs that are less than 24

steps.

ALARM

This alarm function is used to notify the operator that an operation is complete or that a manual

action is required. The program waits until the alarm is acknowledged to proceed. The option is

the alarm number to display.

ATM_INQ

The atmosphere inquiry is used to wait for the actual atmosphere to reach the specified

atmosphere setpoint.

The options are:
• wait, reach within band;

• wait up, reach or exceed the setpoint;

• wait down, reach or be less than the setpoint.

The default band can be set under the

Configuration

menu and is typically 10 (i.e. 0.10 percent

dissociation).
• The

SET_WAIT

opcode will change the band limit

The

LIMIT

opcode immediately following this opcode sets a time limit on the wait.

A

BRANCH

opcode immediately following this opcode can be used to change the program flow

based on the inquiry results.

BRANCH

The

BRANCH

opcode can change program flow based upon an inquiry opcode. The temperature

data is interpreted as the program step if the inquiry is true and the atmosphere data as the

program step if the inquiry is false.

CC_SP_L

The

Cascade Setpoint Limit

opcode will allow the user to set the upper and lower limits for the

cascade setpoint. The temperature data is the lower limit, and the atmosphere data is the upper

limit.

DELAY

This opcode is used when a short delay is needed. The option value is the delay time in seconds

.

DEV_AL

This deviation alarm opcode is used to turn the temperature or atmosphere deviation alarms ON

or OFF.

The option values are:

• OFF, turns OFF both the temperature and atmosphere alarms

• TEMPERATURE, turns ON the temperature alarm and turns OFF the atmosphere alarm