Engineering labels for DC power cords

These labels are affixed to DC cords that provide power for racks, and the protection grounding cables

including the –48V, PGND, and BGND cables. The labels for DC power cords are affixed to one side of

the identification plates on cable ties.

Table 62 Information on labels affixed to DC power cords

Content Meaning

MN(BC)-–48Vn

Loaded cabinet side—Only MN is used to identify the cabinet number (row

number and column number in the equipment room).

Power cabinet side—MN identifies the row and column number of the power

distribution equipment like the control cabinet and distribution box. BC

identifies the row and column number of the –48V connector (if there is no row
number or column number, or the connector can be identified without them,

BC can be omitted). RTN and PGND have no row and column number for

identification.

n—Power port number in down-top and left-right order, in the range of 1 to 3.

MN(BC)-RTN

MN(BC)-PGND

The label only carries location information about the peer equipment, control cabinet, or distribution box,

while the information of the local end is not necessary.

Table 62

lists the information of two –48V power

supplies on the label. The information for other DC voltages (such as 24V, 60V) should be given in similar

methods.
Make sure labels are affixed in the correct direction. After the cable ties are bundled onto the cable, the

identification plates with the labels should face up, and the text on the labels in the same cabinet should

be in the same direction, as shown in

Figure 113

.

Figure 113 Example of labels on a DC power cord

A01/B08––48V2 (loaded cabinet side)—The power cord is –48V2 DC supply, which is from the 8

th

connecter on the second row of –48V bus bar in the cabinet on Row A, and Column 1 in the

equipment room.

B03––48V2 (distribution box side)—The power cord is –48V2 DC supply, which is from the loaded
cabinet on Row B, Column 03 in the equipment room.

In the power distribution box (or the first power cabinet of a row in the transmission equipment room),
every terminal block on the –48V connector bar has a numeric identification. For example, in the above

label of "A01/B08--48V2", "08" (or sometimes "8") is the numeric identification of the terminal block.
PGND and RTN are two copper bars, on which the terminal blocks are short-circuited, so which terminal

is connected makes no difference. You only need to give the row and column numbers of the power
distribution box, instead of giving the specific serial number of the terminal block on the copper bar. For

example, if the label on the loaded cabinet side is "A01-RTN", it means that the power cord is an RTN