9

Installation method

Space requirements

Workbench-mounting

Width of the aisle: ≥ 0.8 m (2.62 ft)

Clearance between the rack and walls or other devices: ≥ 0.8 m (2.62 ft)

Rack-mounting

Clearance between the rack and walls or other devices: ≥ 1.0 m (3.28 ft)

Equipment room height: ≥ 3 m (9.84 ft)

IMPORTANT:

Follow the rack clearance requirements to make sure the switch does not block the rack doors.

H3C recommends that you use a rack with a depth of 1.2 m (3.94 ft) for rack-mounting the switch. For the

chassis space requirements and rack clearance requirements, see

Table 6

,

Figure 5

,

Figure 6

, and

Figure

7

. For more information about switch dimensions, see "

Appendix A Chassis views and technical

specifications

."

Table 6 Rack mounting space requirements

Model

Chassis space requirements

Minimum rack clearance

requirements

S12504 AC/DC

Height: 442 mm (17.40 in)/10 RU

Width: 442 mm (17.40 in)

Depth: 747 mm (29.41 in)

95 mm (3.74 in) between the
front rack post and the inner

side of the front door.

702 mm (27.64 in) between

the front rack post and inner

side of the rear door.

(Including the space for
cabling the power cords.)

S12508/S12518
AC

Height:

{

S12508: 975 mm (38.39 in)/22 RU

{

S12518: 1686 mm (66.38 in)/38 RU

Width: 442 mm (17.40 in)

Depth: 859 mm (33.82 in)

100 mm (3.94 in) between the

front rack post and inner side

of the front door.

769 mm (30.28 in) between

the front rack post and inner

side of the rear door.
(Including the space for

cabling the power cords.)

S12508/S12518
DC

Height:

{

S12508: 975 mm (38.39 in)/22 RU

{

S12518: 1686 mm (66.38 in)/38 RU

Width: 442 mm (17.40 in)

Depth: 759 mm (29.88 in)

100 mm (3.94 in) between the

front rack post and inner side
of the front door.

709 mm (27.91 in) between

the front rack post and inner
side of the rear door.

(Including the space for

cabling the power cords.)