GT490X Engineer’s Reference Guide

21)

Press No. The display will show:-

22)

Press Yes. The display will show:-

Note: Zone Response time is defaulted to 400ms and may not
be changed.

23)

Press Yes. The display will show:-

Note: Zone response time may be programmed as a global
parameter. The default time is 400ms and may be reprogrammed
from 2 to 14 seconds. (increments of 2 seconds).

The time programmed for this option will apply to all zones, there is no option for individual response
times per zone. It is a global setting.

Once the Fault / Mask as been triggered the response time for the Fault / Mask will revert to the
default time of 400ms until the fault / mask problem has cleared.

24)

Press No until the required settings you require are
displayed then press Yes. The display will show:-

Wiring Modes available are.

8 (2 Wire)

Two wires are used for the zone and a global tamper is used.

9 (EOL)

Two wires are used in conjunction with two resistors to give
End Of Line wiring, this is the most secure wiring format.

8+8 (EOL)

This wiring method uses double EOL format to give 16 Zones
from the control panel.

Note: For information on how to wire for the various wiring modes please refer
to the wiring section within this manual.

If selecting 9 (EOL) follow steps 24 through to 26. If selecting 8+8 (EOL) jump to step
28.

25)

With the display showing:-
Press Yes.

26)

The display will show:-

Program Zone
Wiring ?

Zone Response
:400 mS

On-Board Zones
=9<EOL>

Fault / Mask Zones
Response=Norm

On-Board Zones
=9<EOL>

On-Board EOL
=Norm

PR5851 Rev12 490X Eng Ref Guide.qxd 10/05/2012 11:32 Page 22