Mains Wiring - WARNING: Electricity can KILL

Before connecting the control panel ALWAYS disconnect the supply at the consumer
unit. A 230V a.c supply should be taken directly from the consumer unit. In order to
comply with the relevant current wiring regulations this should be via a 3 Amp fused
spur with disconnection facility. This must be carried out by a suitably qualified electri-
cian. If you are in any doubt please contact your local electricity company for advice.
This control panel MUST be Earthed.

Page

5

GT490X Engineer’s Reference Guide

Consumer Unit

3A Unswitched

Fused Spur

Control Panel Mains

Terminal Block

Mains

Connection Colours

Live

= Brown (Red)

Neutral = Blue (Black)
Earth

= Copper

Yellow/Green sleeving should be
used for Copper Earth Conductor

PR5851 Rev12 490X Eng Ref Guide.qxd 10/05/2012 11:32 Page 5