Programming Digicom / Vo-Comm Off/On

Within this section we will program the Digicom and Modem. Both of these devices are
built on the main PCB of the control panel. Only the main functions will be covered
within this Step by Step section.

If required, the 5, 5, Yes, No default may be used to set the basic comms
configuration. When this default is used all other settings that have been
programmed will be returned to factory defaults
. When this default is used the
following will be set.

Digicom Type

Mod+F/F

Modem Mode

No Return

This will allow for connection to GardTec Remote for programming functions.

1)

Enter into Engineer Mode
To do this follow Steps 1 to 4 on page 18
With the display showing:-

2)

Press No five times. The display will show:-

3)

Press Yes. The display will show:-

4)

Press Yes. The display will show:-

Digicom Types available are.

Mod+F/F

Modem enabled and Ademco Fast Format Central
Station protocol enabled.

Mod+SIA

Modem enabled and SIA Central Station protocol enabled.

Mod+PID

Modem enabled and Point ID Central Station protocol
enabled.

For programming details on PID (Point ID Protocol) and SIA please refer to page 91

Program . . . . _ _ _
Zones ?

Program . . . . _ _ _
Digicom ?

Program Digicom
Type or Test ?

Digicom Type . . . .
=Mod+F/F