Henny Penny OEA/OGA-323 User Manual

Page 13

Advertising
background image

Model OFE/OFG-321,322,323,324


2-6. GAS SUPPLY

The fryer and its manual shutoff valve must be disconnected

(Continued)

from the gas supply piping system during any pressure

testing of that system at test pressures in excess of

½ PSIG

(3.45

kPa)

(34.5

mbar).

• The fryer must be isolated from the gas supply piping

system by closing its individual manual shutoff valve

during any pressure testing of the gas supply piping

system at test pressures equal to or less than ½ PSIG

(3.45

kPa)

(34.5

mbar).

• A standard one inch (2.54 cm), black steel pipe and

malleable fittings should be used for gas service connections

for 3 well open fryers, 3/4 inch (1.91 cm) for 2 wells, and 1/2

inch (1.27 cm) for single wells.

• Do not use cast iron fittings.

• Although one inch (2.54 cm) size pipe is recommended for

3 wells, 3/4 inch (1.91 cm) for 2 wells, and 1/2 inch (1.27 cm)

for single wells, piping should be of adequate size and

installed to provide a supply of gas sufficient to meet the

maximum demand without undue loss of pressure between

the meter and the open fryer. The pressure loss in the piping

system should not exceed 0.3 in. water column (0.747 mbar).

Provisions should be made for moving the open fryer for

cleaning and servicing. This may be accomplished by:

1. Installing a manual gas shut off valve and a disconnect

union, or

2. Installing a heavy-duty design A.G.A. certified

connector. In order to be able to service this appliance,

which is provided with casters, a connector complying

with ANSI Z21.69 or CAN 1-6.l0m88 and a

quick-disconnect device, complying with ANSI Z21.41

or CAN 1-6.9m70, must be installed. It must also be

installed with restraining means to guard against

transmission of strain to the connector as specified in

the appliance manufacturer's instruction.

3. See the illustration on the following page for the proper

connection of flexible gas line and cable restraint.

The cable restraint limits the distance the open fryer can be
pulled from the wall. For cleaning and servicing the unit,
the cable must be unsnapped from the open fryer and the
flexible gas line disconnected. This will allow better
access to all sides of the open fryer. The gas line and cable
restraint must be reconnected once the cleaning or
servicing is complete.

703

2-4

Advertising
This manual is related to the following products: