Henny Penny OEA/OGA-323 User Manual

Page 16

Advertising
background image

Model OFE/OFG-321,322,323,324



To avoid electrical shock, do not disconnect the ground

(earth)

plug. This fryer must be adequately and

safely grounded (earthed). Refer to local electrical

codes for correct grounding (earthing) procedures or in

absence of local codes, with The National Electrical

Code, ANSI/NFPA No. 70-(the current edition). In

Canada, all electrical connections are to be made in

accordance with CSA C22.1, Canadian Electrical Code

Part 1, and/or local codes.

Refer to the table below for supply wiring and fusing.

(Per Well)

Volts

Phase

Kw

Amps

200-208 3

14.4

40

220/240 3

14.4

40

440-480 3

14.4

17

380-415 3

14.4

20



To avoid electrical shock, this appliance must be

equipped with an external circuit breaker which will

disconnect all ungrounded (unearthed) conductors.

The main power switch on this appliance does not

disconnect all line conductors.


To avoid electrical shock, this fryer must be

adequately and safely grounded (earthed). Refer to

local electrical codes for correct grounding (earthing)

procedures or in absence of local codes, with The

National Electrical Code, ANSI/NFPA No. 70-(the

current edition). In Canada, all electrical connections are

to be made in accordance with CSA C22.1, Canadian

Electrical Code Part 1, and/or local codes.

CE units require a minimum wire size of 6 mm to be wired
to the terminal block.

Permanently connected electric fryers with casters must be
installed with flexible conduit and a cable restraint, when
installed in the United States. See illustration at left. Holes
are available in the rear fryer frame for securing the cable
restraint to the fryer. The cable restraint does not prevent the
fryer from tipping.

2-7

705

2-10. ELECTRICAL REQUIREMENTS

OFE-320 SERIES

2-9. ELECTRICAL REQUIREMENTS
OFG-320 SERIES (Continued)

DRYWALL CONSTRUCTION
Secure I-bolt to a building stud. Do
not attach to drywall only. Preferred
installation is approximately six
inches to either side of service.
Cable restraint must be at least six
inches shorter than flexible conduit.