8-4

8-3 Measurement of Main Circuit Electrical Quantity

The indicated values depend on the type of meter because the harmonic component is included

in the voltage and current of the main circuit power (input) and the output (motor) side of the
inverter. When measuring with a meter for commercial power frequency use, use the meters
shown in Table 8.3.1.

The power-factor cannot be measured using power-factor meters currently available on the

market, which measure the phase difference between voltage and current. When power-factors
must be measured, measure the power, voltage, and current on the input side and output side,
then calculate the power-factor using the following formula:

Power

factor

Power W

3

Voltage V

Current A

100

=

Ч

Ч

Ч

[ ]

[ ]

[ ]

[%]

Table 8-3-1 Meters for measuring main circuit

Input (power supply) side

Output (motor) side

DC link circuit
voltage
(P(+) - N(-))

Item

Voltage Current*


Voltage Current

Meter
name

Ammeter

A

R,S,T

Voltmeter

V

R,S,T

Powermeter

W

R,S,T

Ammeter

A

U,V,W

Voltmeter

V

U,V,W

Powermeter

W

U,V,W

DC voltmeter

V

Meter
type

Moving-iron

type

Rectifier or

moving-iron

type

Digital
power meter

Moving-iron

type

Rectifier type

Digital power
meter

Moving-coil

type

Symbol

Note: When measuring the output voltage using a rectifier type meter, an error may occur.

Use a digital AC power meter to ensure accuracy.












Fig 8-3-1 Connection of the meters