7) external thermal relay tripped, 8) inverter unit overload and motor overload – Fuji Bikes FRENIC 5000G11S/P11S User Manual

Page 99

Advertising
background image

7-3

YES

YES

NO

Is PTC operating?

Incorrect motor load or
inadequate cooling.
Check the motor side.

Faulty inverter or error
due to noise, etc.
Contact Fuji Electric.

External thermal relay tripped

OH2

Is PTC level
H27 set correctly?

Is PTC MODE
H26 enabled?

YES

NO

NO

Change to regular
external circuit.

Is the external circuit
(including constants)
regular?

Set to correct
value.

NO

YES

(7) External thermal relay tripped

YES

NO

Connect a thermal
O/L relay externally.

Is the electronic thermal
O/L relay setting correct?

Set to the correct level

Is the load excessive?

Inverter unit

overload OLU

Motor overload

OL1, OL2

Do the characteristics
of the electronic thermal
O/L relay and motor
overload match?

NO

NO

YES

YES

Reduce the load or
increase inverter
capacity

Faulty inverter or error
due to noise, etc.
Contact Fuji Electric.

(8) Inverter unit overload and motor overload

NO

YES

NO

NO

Is the load excessive?

Reduce the load.

Is the cooling
fan rotating?

Replace the cooling fan.

Check the temperature of
the heatsink using the alarm
information displayed
on the keypad panel.

Remove obstacles.

Faulty detection
circuit on PCB.
Contact Fuji Electric.

Overtemperature

at inside air OH3

Does the heatsink
temperature indicate

YES

YES

YES

Faulty inverter or error
due to noise, etc.
Contact Fuji Electric.

YES

Is the ambient
temperature within
the specification?

Arrange peripheral
conditions to meet
the specification.

Overheating

at heatsink OH1

NO

NO

Is the cooling air
passage blocked?

(6) Overtemperature at inside air

and overheating at heatsink.

YES

Connect the alarm
signal contact.

Is the alarm function
of the external
equipment operating
correctly?

Faulty inverter or error
due to noise, etc.
Contact Fuji Electric.

YES

Remove the cause
of alarm function
activation.

NO

NO

Is data input to
the control terminals
THR-X1 to X9?
Are alarm signals from
external equipment
input to the terminals
and the CM?

NO

YES

YES(30HP or less)

no

NO

YES

YES

NO

YES

NO

NO

YES

YES

NO

NO

YES

NO

NO

YES

Overtemperature

at inside air OH3

Overheating

at heatsink OH1

Is between the control
terminals 13-11 closed?

Check the temperature of
the heatsink using the alarm
information displayed
on the keypad panel.

Remove the short circuit.

Check the keypad panel display.
Display limit or not?
30HP or less: 20 degrees C.
(40HP or more: 50 degrees C)

Is the cooling fan
for mixing inside air
rotating?
(40HP or more)

Is the peripheral
temperature of the
inverter –10 degrees C
or less ?

Is between the control
terminals 13-11 closed?

Faulty detection
circuit on PCB.
Contact Fuji Electric.

Make peripheral
temperature of the
inverter to meet
the specification.

Is the load excessive?

Reduce the load.

Replace the cooling fan.

Is the cooling

fan rotating?

Replace the cooling fan
for mixing inside air.

Is the cooling fan
for mixing inside air
rotating?
(40HP or more)

Remove obstacles.

Is the cooling air

passage blocked?

Faulty inverter or error
due to noise, etc.
Contract Fuji Electric.

Is the ambient
temperature within
the specification ?

Arrange peripheral
conditions to meet
the specification.

(6) Overtemperature at inside air

and overheating at heatsink.

YES(30HP or less)

Advertising