6-2

6-2 Alarm Reset

To release the trip status, enter the reset command

by pressing the key on the keypad panel or
inputting signal from the terminal (RST) of the control
terminals after removing the cause of the trip. Since
the reset command is an edge operation, input a
command such as !!OFF-ON-OFF!! as shown in
Fig.6-2-1.
When releasing the trip status, set the operation
command to OFF. If the operation command is set
to ON, inverter will start operation after resetting.


WARNING

If the alarm reset is activated with the operation signal ON, the inverter will restart suddenly, which
may be dangerous. To ensure safety, disable the operating signal when releasing the trip status.
as accident may result.


Reset command

OFF ON OFF

Keypad panel display

Normal

display

Alarm display

(Operable)

Alarm output

OFF ON OFF


Fig.6-2-1

10ms or

Trip

RESET