Fuji Bikes FRENIC 5000G11S/P11S User Manual

Page 38

Advertising
background image

4-6

The function code consists of alphanumeric characters. Unique alphabetical letters are assigned for each
function group.

Table 4-3-1

Function code

Function

Remarks

F00 - F42

Fundamental Functions

E01 - E47

Extension Terminal Functions

C01 - C33

Control Functions of Frequency

P01 - P09

Motor Parameters

H03 - H39

High Performance Functions

A01 - A18

Alternative Motor Parameters

U01 - U61

User Functions

o01 - o55

Optional Functions

Can be selected only with an option connected


To scroll “Function Select” screen rapidly , use + or + to move the screen in a unit grouped by
alphabet.









Select the desired function and press to switch to the “data setting” screen.

On the “data setting” screen, the data values on the LCD can be increased or decreased in the smallest

possible unit by pressing or Holding down or expands the rate of change, thereby
enabling values to be modified more rapidly. Otherwise, select the digit to be modified using

, then set

data directly. When data is modified, the value before modification will be displayed at the same time for
reference purpose. To save the data, press . Pressing cancels the changes made and
returns to the “Function Select” screen. The modified data will be effective in inverter operation after the
data is saved by . The inverter operation does not change only if data is modified. When data
setting is disabled in the case of “Data protected” or “Data setting invalid during inverter running,” make
necessary changes. Data cannot be modified for the following reasons :

Table 4-3-2

Display

Reason for no modification

Release method

LINK ACTIVE

Currently writing from RS-485/link
option to Function is being made.

Send a cancel command of function
writing from RS-485. Stops a
“Write” operation from the link.

NO SIGNAL(WE)

The edit enabling command function
is selected using a general-purpose
input terminal.

Among functions E01 to E09, turn the
terminal of data 19 (edit enabling
command selection) ON.

DATA PRTCTD

Data protection is selected for function
F00.

Change function F00 to 0.

INV RUNNING

An attempt is made to change a
function that cannot be changed
during inverter operation.

Stop inverter operation.

FWD/REV ON

An attempt is made to change a
function that cannot be changed
with the FWD/REV command on.

Turn FWD/REV command off.

FUNC
DATA

FUNC
DATA

>>

RESET

>>

F00DATA PRTC

F01

FREQ CMD 1

F02

OPR METHOD

F03

MAX Hz-1

A18

SLIP COMP2

F00DATA PRTC

F01

DATA PRTC

F02

OPR METHOD

F42

TRQVECTOR1

E01X1 FUNC

E02

X2 FUNC

E03

X3 FUNC

F00

DATA PRTC

F01FREQ CMD 1

F02

PPR METHOD

F03

MAX Hz-1

+

+

>>

>>

>>

FUNC
DATA

Advertising