Caution – Fuji Bikes FRENIC 5000G11S/P11S User Manual

Page 61

Advertising
background image

5-14



‹

This function sets the upper and lower limits for the

setting frequency .


Setting range G11S: 0 to 400Hz

P11S: 0 to 120Hz












Upper limit value

Lower limit value

Lower limit value

Upper limit value

Set frequency

Set frequency

+ Maximum frequency

- Maximum frequency

+100%

-

100%

The inverter output starts with the start frequency when

operation begins, and stops with the stop frequency
when operation ends.

If the upper limit value is less than the lower limit value,

the upper limit value overrides the lower limit value.

When lower limit value is set, the inverter operates with

lower limit value at operation command is "ON" even
frequency command is zero(0Hz).



‹

This function sets the rate of the set frequency value

to analog input.


Operation follows the figure below.

4 20[mA]

-10 0 +10[V]

Set frequency value

Analog input
+10V terminal 12
20mA terminal C1

200%

100%

50%

+Maximum
frequency

-Maximum
frequency

‹

This function adds a bias frequency to the set
frequency value to analog input.

Setting range G11S: -400.0 to +400.0Hz

P11S: -120.0 to +120.0Hz

The operation follows the figure below.
When the bias frequency is higher than the maximum
frequency or lower than the - maximum frequency, it is
limited to the maximum or - maximum frequency.

4 20[mA]

-10 0 +10[V]

Set frequency value

Analog input
+10V terminal 12
20mA terminal C1

Bias frequency
(when positive)

Bias frequency
(when negative)

+Maximum
frequency

-Maximum
frequency


Reversible operation is valid if the function code

F01/C30 is set to "4" or "5" only.

This function is invalid if PID control is selected(H20 is

"1" or "2").






‹

Starting frequency: This function sets the frequency

with which to start a DC injection brake to decelerate
the motor to a stop.


Setting range: 0 to 60Hz
‹

Operation level: This function sets the output current

level when a DC injection brake is applied. Set a
percentage of inverter rated output current in 1% steps.

Setting range G11S: 0 to 100%

P11S: 0 to 80%

‹

Time: This function sets the time of a DC injection

brake operation.



Setting range 0.0: Inactive

0.1 to 30.0 seconds

CAUTION

Do not use the inverter brake function for

mechanical holding.

Injury may result.

F20

DC brake (starting frequency)

DC brake (Braking level)

DC brake (Braking time)

F21

F22

F18

Bias frequency

Frequency limiter (High)

F15

F16

Frequency limiter (Low)

F 1 8

F R E Q

B I A S

F 1 5

H L I M I

T E R

F 1 6

L L I M I

T E R

F 1 7

F R E Q G A I N

F 2 0

D C

B R K H z

F 2 1

D C

B R K

L V L

F 2 2

D C

B R K

t

F17

Gain

Advertising