7.Trouble shooting

7.1 Protective function activation

(1) Overcurrent

YES

NO

NO

NO

YES

NO

NO

NO

YES

YES

YES

Are the motor connecting terminals (U, V, W) short-circuited or grounded?

Reduce the load or increase

the inverter capacity.

Is the load excessive?

Can the torque boost

amount be reduced?

Remove the short-circuit

and ground fault.

Prolong time settings.

Faulty inverter or error

due to noise.

Consult with Fuji Electric.

Reduce the load or increase

the inverter capacity.

Is the torque boost

correct?

Reduce the torque boost.

Is the acceleration time

setting too short

compared with the load?

YES

Has the load changed

suddenly?

NO

NO

NO

YES

NO

Can the deceleration time
setting be prolonged?

YES

NO

The braking method

requires inspection.

Contact Fuji Electric.

Reduce the load or increase
the inverter capacity.

YES

Overcurrent

during acceleration

OC1

Is the deceleration time

setting too short compared

with the load?

Can the acceleration time

setting be prolonged?

YES

Overcurrent

during deceleration

OC2

Overcurrent

running at constant speed

OC3

NO

(2) Ground fault

Note:The ground fault protective function is provided only for inverter for nominal applied motors rated at 40HP or more.



(3) Fuse brown

Fuse brown

FUS

Possible short-circuit

within the inverter.

Contact Fuji Electric.

Ground fault

EF

Remove the grounded part.

YES

Faulty inverter or error due to noise.

Contact Fuji Electric.

NO

Is a part in the inverter output

circuit (cable, motor) grounded?