Warning – Fuji Bikes FRENIC 5000G11S/P11S User Manual

Page 84

Advertising
background image

5-37

‹

Instantaneous switching to another power line (when the

power of an operating motor is cut off or power failure

occurs) creates a large phase difference between the

line voltage and the voltage remaining in the motor,

which may cause electrical or mechanical failure. To

rapidly switch power lines, write the remaining voltage

attenuation time to wait for the voltage remaining in the

motor to attenuate. This function operates at restart

after a momentary power failure.

H 1 3

R E S T A R T T

Setting range: 0.1 to 5.0 seconds

‹

When the momentary power failure time is shorter than

the wait time value, a restart occurs following the wait

time. When the power failure time is longer than the

wait time value, a restart occurs when the inverter is

ready to operate (after about 0.2 to 0.5 second).

‹

This function determines the reduction rate of the output

frequency for synchronizing the inverter output frequency

and the motor speed. This function is also used to

reduce the frequency and thereby prevent stalling under

a heavy load during normal operation.

H 1 4

F A L L R A T E

Setting range: 0.00, 0.01 to 100.00 Hz/s

‹

When 0.00 is set, the frequency is reduced according to
the set deceleration time.

Note:
A too large frequency reduction rate is may temporarily
increase the regeneration energy from the load and
invoke the overvoltage protective function. Conversely,
a rate that is too small extends the operation time of the
current limiting function and may invoke the inverter
overload protective function.



‹

This function is for when 2 (deceleration-to-stop at power

failure) or 3 (operation continuation) is set to "F14

Restart after momentary power failure (operation

selection)." Either function starts a control operation if

the main circuit DC voltage drops below the set operation

continuation level.

H 1 5

H

O

L

D V

Setting range 230 V series: 200 to 300V

460 V series: 400 to 600V

‹

When power supply voltage to the inverter is high,

control can be stabilized even under an excessive load

by raising the operation continuation level. However,

when the level is too high, this function activates during

normal operation and causes unexpected motion.

Please contact Fuji electric when changing the initial

value.

‹

As the power to an external operation circuit (relay

sequence) and the main power to the inverter is

generally cut off at a power failure, the operation

command issued to the inverter is also cut off. This

function sets the time an operation command is to be

held in the inverter. If a power failure lasts beyond the

self-hold time, power-off is assumed, automatic restart

mode is released, and the inverter starts operation at

normal mode when power is applied again. (This time

can be considered the allowable power failure time.)

H 1 6

S E L

F

H

O L D T

Setting range: 0.0 to 30.0 seconds, 999

When "999" is set, an operation command is held (i.e.,
considered a momentary power failure) while control power
in the inverter is being established or until the main circuit
DC voltage is about 100Vdc.

‹

This function controls motor torque according to a

command value.

Set value

Operation

0

Inactive (Operation by frequency command)

1

Torque control active
0 to +10V analog voltage input to terminal 12
and the direction of rotation (FWD or REV) is
used for the torque command value. 0 is
used for 0 to -10V.

2

Torque control active
-10 to +10V analog voltage input to terminal
12 and the direction of rotation (FWD or
REV) is used for the torque command value.

x

F o rw a rd c o m m a n d
R e ve rs e c o m m a n d

T o rq u e

lim ita tio n

D e te c te d to rq u e

c u rre n t

R e g u la to r

V o lta g e a t

te rm in a l 1 2

O u tp u t

fre q u e n c y

+

-

T o rq u e c o m m a n d va lu e

T o rq u e c o n tro l b lo c k d ia g ra m

The torque command value is +200% when the voltage at
terminal 12 is +10V and is -200% when the voltage is -10V.
‹

Auto tuning(P04/A13: 2) should be done to use this

function.

‹

In torque control, the torque command value and motor

load determine the speed and direction of rotation.

‹

When the torque is controlled, the upper limit of

frequency refers to the minimum value among the

maximum frequency , the frequency limiter (upper limiter)

value, and 120 Hz. Maintain the frequency at least

one-tenth of the base frequency because torque control

performance deteriorates at lower frequencies.

‹

If the operation command goes off during a torque

control operation, the operation is switched to speed

control and the motor decelerates-to-stop. At this time,

the torque control function does not operate.

‹

This function cannot be used when the motor 2 is

selected.

‹

This function cannot be used for FRN-P11S.

WARNING

The malfunction may be occurred
when the set torque is mistaken. (up
to upper frequency, maximum
frequency or 120Hz)
as accident may result.

‹

This function automatically extends accelerating time

against acceleration operation of 60 seconds or longer to

prevent an inverter trip resulting from a temperature rise

in inverter due to overcurrent.

Set value 0: Inactive

1: Active

(When the active drive function is activated, the
acceleration time is three times the selected time.)

H 1 8

T R Q

C T R L

H 1 9

A U T

R E D

H19

Active drive

H16

Auto-restart (OPR command selfhold time)

H13

Auto-restart (Restart time)

H15

Auto-restart (Holding DC voltage)

H14

Auto-restart (Freq. fall rate)

H18

Torque control

Related functions

E01toE09

(Set value: 23)

Advertising