Fuji Bikes FRENIC 5000G11S/P11S User Manual

Page 26

Advertising
background image

2-14

Pulse output

FMP
(CM:
Common
terminal)

Frequency monitor
(pulse waveform output)

Outputs a monitor signal using the pulse waveform.
This signal has the same function as the FMA signal.

Y1 Transistor

output1

Y2 Transistor

output2

Y3 Transistor

output3

Y4 Transistor

output4

A running signal, frequency equivalence signal, overload early warning
signal, and other signals from the inverter are output (as transistor
output) to arbitrary ports, For details, see "Setting the Terminal
Functions E20 to E23" in Section 5.2, "Details of Each Function."

<Specifications of transistor output circuit>

*

Item min.

typ.

max.

ON level

-

2V

3V

Operating
voltage

OFF level

-

24V

27V

Maximum load current at ON level

-

-

50mA

Leakage current at OFF level

-

-

0.1mA

Transistor

output

CME Transistor

output

common

Common terminal for transistor output signals
This terminal is insulated from terminals [CM] and [11].

30A,30B,
30C

Alarm output for any fault

If the inverter is stopped by an alarm (protective function), the alarm
signal is output from the relay contact output terminal (1SPDT).
Contact rating: 48V DC, 0.5A
An excitation mode (excitation at alarm occurrence or at normal
operation) can be selected.

Relay output

Y5A,Y5C Multipurpose-signal

relay

output

These signals can be output similar to the Y1 to Y4 signals above.
The contact rating for any fault is the same as that of the alarm output
above.
An excitation mode (excitation at alarm occurrence or at normal
operation) can be selected.

DX+, DX- RS-485 communication

input-output

Input-output signal terminals for RS-485 communication. UP to 31
inverters can be connected using the daisy chain method.

Communication

SD Communication-cable

shield connection terminal

Terminal for connecting the shield of a cable. The terminal is
electrically floating.


(1)Analog input terminals (13,12,V2,C1,and 11)

These terminals receive weak analog signals that may be
affected by external noise. The cables must be as short as
possible (66ft (20m) or less), must be shielded, and must
be grounded in principle. If the cables are affected by
external induction noise, the shielding effect may be
improved by connecting the shield to terminal [11].


If contacts must be connected to these circuits, twin

(bifurcated type) contacts for handling weak signals must
be used. A contact must not be connected to terminal
[11].


If an external analog signal output device is connected to
these terminals, it may malfunction as a result of inverter
noise. To prevent malfunction, connect a ferrite core or
capacitor to the external analog signal output device.



Fig. 2-3-12

Fig. 2-3-13 Example of noise prevention

0k to 5 kΩ

Advertising