3-13 data copy – Fuji Bikes FRENIC 5000G11S/P11S User Manual

Page 45

Advertising
background image

4-13

4-3-13 Data copy

On the "Program menu" screen, select "9. Data Copy" to display the data copy read screen. A copy
operation is then performed in the following order;reading inverter function data, removing the keypad panel,
attaching the keypad panel to another inverter, and writing the data to the inverter.
The "verify" feature also makes it possible to compare and check differences in the data stored in the keypad
panel and the data stored in the inverter.


DATA copy screen

Mode (read mode)

60.00

RUN

PRG

⇒PRG MENU

F/D

⇒LED SHIFT

60.00

1.DATA SETTING
2.DATA CHECK
3.OPR MNTR
4.I/O CHECK

5.MAINTENANC
6.LOAD FCTR
7.ALM INF
8.ALM CAUSE
⇒9.DATA COPY

Write data

Read data

<DATA COPY>

-----
READ

<DATA COPY>

-----
READ

„„„„

Reading

<DATA COPY>

040HP-4
READ
COMPLETE

„„„„„„„„„„„„„„

Remove keypad panel

Data of inverter type
read by keypad panel

Read complete

60.00

RUN

PRG

⇒PRG MENU

F/D

⇒LED SHIFT

<DATA COPY>

040HP-4
READ

<DATA COPY>

040HP-4
WRITE

Mode (write mode)

<DATA COPY>

040HP-4
WRITE

„„„„

Attach keypad panel,

Turn power ON.

Writing

<DATA COPY>

040HP-4
WRITE
COMPLETE

„„„„„„„„„„„„„„„„

Write
complete

When WRITE to the type of the inverter (capacity,
voltage and series) is same as the inverter type in
copy origin, all of the function will be written. When
the type of the inverter is different, the function
except the following will be written. However, in both
cases,

F00(Data protection), P02/A11(Motor capacity),

P04/A13 (Motor tuning), H03(Data initializing), H31(RS-485
address) and o26/AIO optional adjustment will NOT be
written.

- The function which will NOT be copied when different inverter type

FUNC.

NAME FUNC. NAME

F03

Max. freq. 1

F26

Motor sound

F04

Base freq. 1

E33

OL function

(Mode select)

F05

Rated voltage 1

E34

OL function

(Level)

F06

Max. voltage 1

E35

OL function

(Timer)

F09

Torque boost 1

E37

OL2 function

(Level)

F10

Electronic
thermal 1

(Select)

H15

Auto-restart

(Holding DC

voltage)

F11

Electronic
thermal 1

(Level)

All of
"P"
code

Motor 1

F12

Electronic
thermal 1

(Thermal time

constant)

All of
"A"
code

Motor 2

F13 Electronic

thermal
overload relay

In addition, when WRITE from inverter ROM No. is new one to old
one, WRITE except F01(Freq. command 1) without ERROR display.

60.00

1.DATA SETTING
2.DATA CHECK
3.OPR MNTR
4.I/O CHECK

5.MAINTENANC
6.LOAD FCTR
7.ALM INF
8.ALM CAUSE
⇒9.DATA COPY

Inverter type of data
stored by keypad panel

<DATA COPY>
040HP-4

WRITE

MEMORY ERROR

„„„„

<DATA COPY>
040HP-4

WRITE

MEMORY ERROR

WRITE to the inverter with different
capacity, voltage and series.

FUNC
DATA

FUNC
DATA

FUNC
DATA

FUNC
DATA

FUNC
DATA

FUNC
DATA

PRG

PRG

PRG