P:motor parameters, H:high performance functions – Fuji Bikes FRENIC 5000G11S/P11S User Manual

Page 50

Advertising
background image

5-3

Factory setting

Func

No.

NAME

LCD Display

Setting range

Unit

Min.

Unit

-30HP 40HP-

Change

during op

User

Set value

Remark


C20 JOG

frequency

C20

JOG Hz

G11S:0.00 to 400.00Hz

Hz

0.01

5.00

A

P11S:0.00 to 120.00Hz

C21 PATTERN(Mode

select)

C21

PATTERN 0,1,2

-

-

0

NA

operation

C22 (Stage

1)

C22

STAGE 1

Operation time:0.00 to 6000s

s

0.01

0.00 F1

A

C23 (Stage

2)

C23

STAGE 2

F1 to F4 and R1 to R4

0.00 F1

A

C24 (Stage

3)

C24

STAGE 3

0.00 F1

A

C25 (Stage

4)

C25

STAGE 4

0.00 F1

A

C26 (Stage

5)

C26

STAGE 5

0.00 F1

A

C27 (Stage

6)

C27

STAGE 6

0.00 F1

A

C28 (Stage

7)

C28

STAGE 7

0.00 F1

A

C30 Frequency command 2

C30

FREQ CMD 2

0 to 11 -

-

2

NA

C31 Offset

adjust(terminal[12])

C31

BIAS 12

-100.0 to +100.0%

%

0.1

0.0

A

C32

C32

GAIN 12

0.0 to +200.0%

%

0.1

100.0

A

C33 Analog setting signal filter

C33

REF FILTER

0.00 to 5.00s

s

0.01

0.05

A

P:Motor Parameters

P01 Number of motor 1 poles

P01

M1 POLES

2 to 14

-

2

4

NA

P02 Motor

1

(Capacity)

P02

M1-CAP

Up to 30[HP]: 0.01 to 60HP

HP

0.01

Motor Capacity

NA

40[HP]and above: 0.01 to 800HP

P03

(Rated current)

P03

M1-Ir

0.00 to 2000A

A

0.01

Motor rated current

NA

P04

(Tuning)

P04

M1 TUN1

0, 1, 2

-

-

0

NA

P05

(On-line Tuning)

P05

M1 TUN2

0, 1

-

-

0

NA

P06

(No-load current)

P06

M1-Io

0.00 to 2000A

A

0.01

NA

Fuji STANDARD RATED

VALUE

P07

(%R1

setting)

P07

M1-%R1

0.00 to 50.00%

%

0.01

A

Fuji STANDARD RATED

VALUE

P08 (%X

setting)

P08

M1-%X

0.00 to 50.00%

%

0.01

A

Fuji STANDARD RATED

VALUE

P09 Slip compensation control 1

P09

SLIP COMP1

0.00 to 15.00Hz

Hz

0.01

0.00

A

H:High Performance Functions

H03 Data

initializing

H03

DATA INIT

0, 1

-

-

0

NA

H04 Auto-reset

(Times)

H04

AUTO-RESET

0, 1 to 10 times

-

1

0

A

H05 (Reset

interval)

H05

RESET INT

2 to 20s

s

1

5

A

H06 Fan stop operation

H06

FAN STOP

0, 1

-

-

0

A

H07 ACC/DEC

pattern

(Mode select)

H07

ACC PTN

0,1,2,3

-

-

0

NA

H08 Rev. phase sequence lock

H08

REV LOCK

0, 1

-

-

0

NA

H09 Start

mode

H09

START MODE

0, 1, 2

-

-

0

NA

H10 Energy-saving

operation

H10

ENERGY SAV

0, 1

-

-

G11S:0

A

P11S:1

H11 DEC

mode

H11

DEC MODE

0, 1

-

-

0

A

H12 Instantaneous OC limiting

H12

INST CL

0, 1

-

-

1

NA

H13 Auto-restart

(Restart time)

H13

RESTART t

0.1 to 10.0s

s

0.1

0.1

NA

H14

(Freq. fall rate)

H14

FALL RATE

0.00 to 100.00Hz/s

Hz/s

0.01

10.00

A

H15

(Holding DC voltage)

H15

HOLD V

3ph 230V class: 200 to 300V

V

1

230V class:235V

A

3ph 460V class: 400 to 600V

460V class:470V

H16

(OPR command selfhold time)

H16

SELFHOLD t

0.0 to 30.0s, 999

s

0.1

999

NA

H18 Torque

control

H18

TRQ CTRL

G11:0, 1, 2, P11:0

-

-

0

NA

H19 Active

drive

H19

AUT RED

0, 1

-

-

0

A

H20 PID

control

(Mode select)

H20

PID MODE

0, 1, 2

-

-

0

NA

H21

(Feedback signal)

H21

FB SIGNAL

0, 1, 2, 3

-

-

1

NA

H22 (P-gain)

H22

P-GAIN

0.01 to 10.00 times

-

0.01

0.1

A

H23

(I-gain)

H23

I-GAIN

0.0 , 0.1 to 3600s

s

0.1

0.0

A

H24 (D-gain)

H24

D-GAIN

0.00s , 0.01 to 10.0s

s

0.01

0.00

A

H25 (Feedback

filter)

H25

FB FILTER

0.0 to 60.0s

s

0.1

0.5

A

H26 PTC

thermistor

(Mode select)

H26

PTC MODE

0, 1

0 A

H27 (Level)

H27

PTC LEVEL

0.00 to 5.00V

V

0.01

1.60

A

H28 Droop

operation

H28

DROOP

G11:-9.9 to 0.0Hz, P11:0.0 (Fixed.)

Hz

0.1

0.0

A

H30 Serial link

(Function select)

H30

LINK FUNC

0, 1, 2, 3

-

-

0

A

H31 Modbus-RTU

(Address)

H31

ADDRESS

0 (broadcast), 1 to 247

-

1

1

NA

H32

(Mode select on no response error)

H32

MODE ON ER

0, 1, 2, 3

-

-

0

A

H33

(Timer)

H33

TIMER

0.0 to 60.0s

s

0.1

2.0

A

H34

(Baud

rate)

H34

BAUD RATE

0, 1, 2, 3

-

-

1

A

H35

(Data

length)

H35

LENGTH

0 (8-bit fixed)

-

-

0

A

H36

(Parity

check)

H36

PARITY

0, 1, 2

-

-

0

A

H37

(Stop

bits)

H37

STOP BITS

0(2bit), 1(1bit)

-

-

0

A

H38

(No response error detection time)

H38

NO RES t

0 (No detection), 1 to 60s

s

1

0

A

H39 (Response

interval)

H39

INTERVAL

0.00 to 1.00s

s

0.01

0.01

A