2) three-phase 460v series – Fuji Bikes FRENIC 5000G11S/P11S User Manual

Page 111

Advertising
background image

9-2

(2) Three-phase 460V series

Nominal applied

motor [HP]

0.5 1 2

3 5 7.5 10 15 20 25 30 40 50 60 75 100 125 150 200 250 300 350 400 450 500 600 700 800

Type
FRN[][][]G11S-4UX

F50 001 002 003 005 007 010 015 020 025 030 040 050 060 075 100 125 150 200 250 300 350 400 450 500 600

-

-

Rated output
capacity (*1) [kVA]

1.2 2.0 2.9 4.4 7.2 10 14 19 24 31 36 48 60 73 89 120 140 167 202 242 300 331 414 466 518 590

-

-

Rated output
current (*2) [A]

1.5 2.5 3.7 5.5 9 13 18 24 30 39 45 60 75 91 112 150 176 210 253 304 377 415 520 585 650 740

-

-

Overload
capability

150% of rated output current for 1 min.
200% of rated output current for 0.5 s

150% of rated output current for 1 min.
180% of rated output current for 0.5 s

Starting torque

200% or more (under torque vector control)

180% or more (under torque vector control)

Braking torque
(*3) [%]

50% or more

100% or more

20% or more

10 to 15%

Braking time [s]

5

5

No limit

Braking duty
cycle [%ED]

5 3 5 3 2 3 2

No

limit

G11

Mass [lbs (kg)]

4.9

(2.2)

5.5

(2.5)

8.4

(3.8)

8.4

(3.8)

8.4

(3.8)

14

(6.5)

14

(6.5)

22

(10)

22

(10)

23

(10.5)

23

(10.5)

64

(29)

75

(34)

86

(39)

88

(40)

106

(48)

154
(70)

154

(70)

220

(100)

220

(100)

309

(140)

309

(140)

705

(320)

705

(320)

904

(410)

904

(410)

-

-

Type
FRN[][][]P11S-4UX

-

-

-

-

- 007 010 015 020 025 030 040 050 060 075 100 125 150 200 250 300 350 400 450 500 600 700 800

Rated capacity (*1)
[kVA]

-

-

-

-

- 10 13 18 24 29 35 48 60 73 89 120 140 167 202 242 300 331 386 414 518 590 669 765

Rated output
current (*2) [A]

-

-

-

-

- 12.5 16.5 23 30 37 44 60 75 91 112 150 176 210 253 304 377 415 485 520 650 740 840 960

Overload
capability

110% of rated output current for 1 min.

Starting torque

50% or more

Braking torque
(*3) [%]

Approx. 20%

Approx. 10 to 15%

Braking time [s]

No limit

Braking duty
cycle [%ED]

No limit

P11

Mass [lbs (kg)]

- - - - -

13

(6.1)

13

(6.1)

13

(6.1)

22

(10)

22

(10)

23

(10.5)

64

(29)

64

(29)

75

(34)

86

(39)

88

(40)

106

(48)

154

(70)

154

(70)

220

(100)

220

(100)

309

(140)

309

(140)

309

(140)

705

(320)

705

(320)

904

(410)

904

(410)

Rated output
voltage(*4) [V]

3-phase, 380V, 400V, 415V(440V)/50Hz, 380V, 400V, 440V, 460V/60Hz

Output

ratings Rated output

frequency [Hz]

50,60Hz

Phases, voltage,
frequency

3-phase,380 to 480V,50/60Hz

3-phase, 380 to 440V/50Hz *5)
3-phase, 380 to 480V/60Hz

Voltage/frequency
variations

Voltage: +10% to -15% (Imbalance rate between phases: 2% or less (*6) , Frequency: +5% to -5%

Momentary voltage
dip capability (*7)

Operation will continue with 310V or more. If voltage drops below 310V, operation will continue for up to 15 ms.
If "Continuous operation" is selected, the output frequency will be lowered to withstand the load until normal voltage is resumed.

Input ratings

Required power
supply
capacity (*8)[kVA]

0.7 1.2 2.2 3.1 5.0 7.2 9.7 15 20 24 29 38 47 57 70 93 111 136 161 196 244 267 341 383 433 488 549 610

(*1) Indicated capacities are at the rated output voltage 230V for the 230V series and 460V for the 460V series. The rated capacity will

be lowered if the supply voltage is lowered.

(*2) In the case of a low impedance load, such as a high-frequency motor, the current may drop below the rated current.
(*3) Indicates when a nominal applied motor is used (the average torque when decelerated to stoppage from 60 Hz, which varies

depending on motor loss).

(*4) An output voltage exceeding the supply voltage cannot be generated.
(*5) The taps within the inverter must be changed for a power supply rated at 380 to 398V/50 Hz or 380 to 430V/60 Hz.
(*6) If the imbalance between phases exceeds 2%, use a power-factor correcting DC reactor (DCR).

( Max. Voltage [V] - Min. Voltage [V] )

Imbalance rate between phases [%] = x 67[%]

3-phase average voltage [V]

(*7) Test was conducted under the standard load conditions stipulated by the JEMA committee (at the load equivalent to 85% of the

nominal applied motor).

(*8) Indicates the values required when using a power-factor correcting DC reactor (DCR) (optional for inverters of 75HP or less) with a

loaded nominal applied motor.

Advertising