Fuji Bikes FRENIC 5000G11S/P11S User Manual

Page 121

Advertising
background image

9-12

Data format [10]

Alarm Code

Code Description Code

Description

0

No alarm

-

22

Overheat, DB resistor

dbH

1

Overcurrent, during acceleration (INV output )

OC1

23

Overload, motor 1

OL1

2

Overcurrent, during deceleration (INV output )

OC2

24

Overload, motor 2

OL2

3

Overcurrent, during steady state operation
(INV output )

OC3 25

Overload,

inverter

OLU

5 Ground

fault

EF 27 Overspeed

OS

6

Overvoltage, during acceleration

OU1

28

PG wire break

Pg

7

Over voltage, during deceleration

OU2

31

Memory error

Er1

8

Overvoltage, during steady state operation

OU3

32

Keypad error

Er2

10 DC

undervoltage

LU

33 CPU

error

Er3

11

Power supply open phase

Lin

34

Option comm. error

Er4

14

Blown DC fuse

FUS

35

Option error

Er5

16 Output

wiring

error

Er7 36 PL

error

Er6

17

Overheat, heat sink, inverter

OH1

37

Output wiring error

Er7

18

Overheat, outside thermal

OH2

38

RS-485 comm. error

Er8

19

Overheat, unit inside temp.

OH3

Data format [11]

Capacity code

Code Capacity

(HP) Code Capacity

(HP)

Code Capacity

(HP)

7 0.07(spare)

2000

20 17500 175

15 0.15(spare)

2500

25

20000 200

25 0.25 3000 30 25000

250

50 0.5

4000 40

30000

300

100 1 5000 50

35000

350

200 2 6000 60

40000

400

300 3 7500 75

45000

450

500 5 10000 100 50000 500
750 7.5 12500 125 60600 600

1000 10 15000 150 60700 700
1500 15

60800

800

Data format [12]

Index data (ACC/DEC time, display coefficient)

15

14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

Polarity

0 0 0

Index

portion

Data portion

0: Positive (+),

0: 0.01 X

001

–999 (0.00–9.99)

1:

0.1

X

100

–999

(10.0

–99.9)

1: Negative ( - )

2: 1

X

100

–999 (100–999)

3:

10

X

100

–999 (1000–9990)



Example: If F07 (acceleration time 1) = 20.0 s

10.0 < 20< 99.9 → index =1
20.0 = 0.1 X 200 → 0400

H

+ 00C8

H

= 04C8

H

Advertising