Specifications, 1 standard specifications, 1 9. specifications – Fuji Bikes FRENIC 5000G11S/P11S User Manual

Page 110: 1) three-phase 230v series

Advertising
background image

9-1

9. Specifications

9-1 Standard Specifications

(1) Three-phase 230V series

Nominal applied motor
[HP]

0.25

0.5

1 2 3 5 7.5

10

15

20

25

30

40

50

60

75

100

125

150

Type
FRN[][][]G11S-2UX

F25 F50

001 002 003 005

007

010

015

020

025

030

040

050 060 075 100

125

-

Rated output
capacity (*1) [kVA]

0.6 1.2

2.0 3.2 4.4 6.8

10

13

18

24

29

35

46

58 72 86 113

138

-

Rated output
current (*2) [A]

1.5 3.0

5.0 8.0 11 17

25

33

46

59

74

87

115

145 180 215 283

346

-

Overload
capability

150% of rated output current for 1 min.
200% of rated output current for 0.5 s

150% of rated output current for 1 min.
180% of rated output current for 0.5 s

Starting torque

200% or more (under torque vector control)

180% or more (under torque vector control)

Braking torque
(*3) [%]

150% or more

100% or more

Approx. 20%

Approx. 10 to 15%

Braking time [s]

10

5

5

No limit

Braking duty
cycle [%ED]

10 5 3 5 3 2 3 2

No limit

G11

Mass [lbs (kg)]

4.9

(2.2)

4.9

(2.2)

5.5

(2.5)

8.4

(3.8)

8.4

(3.8)

8.4

(3.8)

13

(6.1)

13

(6.1)

22

(10)

22

(10)

23

(10.5)

23

(10.5)

64

(29)

79

(36)

97

(44)

101

(46)

154

(70)

254

(115)

-

Type
FRN[][][]P11S-2UX

- - - - - -

007

010

015

020

025

030

040

050

060

075

100

125

150

Rated capacity (*1)
[kVA]

- - - - - - 8.8

12

17

22

27

31

46

58 72 86 113

138

165

Rated output
current (*2) [A]

- - - - - - 22

29

42

55

67

78

115

145 180 215 283

346

415

Overload
capability

110% of rated output current for 1 min.

Starting torque

50% or more

Braking torque
(*3) [%]

Approx. 20%

Approx. 10 to 15%

Braking time [s]

No limit

Braking duty
cycle [%ED]

No limit

P11

Mass [lbs (kg)]

- - - - - -

13

(5.7)

13

(5.7)

13

(5.7)

22

(10)

22

(10)

23

(10.5)

64

(29)

64

(29)

79

(36)

97

(44)

101

(46)

154

(70)

254

(115)

Rated output
voltage (*4) [V]

3-phase, 200V/50Hz, 200V,220V,230V/60Hz

Output

ratings

Rated output
frequency [Hz]

50,60Hz

Phases, voltage,
frequency

3-phase, 200 to 230V, 50/60Hz

3-phase, 200 to 220V, 220 to 230V/50Hz
3-phase, 200 to 230V/60Hz

Voltage/frequency
variations

Voltage: +10% to -15% (Imbalance rate between phases: 2% or less (*6) , Frequency: +5% to -5%

Momentary voltage
dip capability (*7)

Operation will continue with 165V or more. If voltage drops below 165V, operation will continue for up to 15 ms.
If "Continuous operation" is selected, the output frequency will be lowered to withstand the load until normal voltage is resumed.

Input ratings

Required power
supply
capacity (*8)[kVA]

0.4 0.7

1.3 2.2 3.1 5.0

7.2

9.7

15

20

24

29

38

47 56 69 93

111

134

Advertising