Fuji Bikes FRENIC 5000G11S/P11S User Manual

Page 56

Advertising
background image

5-9

‹

This function sets the maximum output frequency for
motor 1.

‹

This is a function for motor 1.


Setting range G11S: 50 to 400 Hz

P11S: 50 to 120Hz

Setting a value higher than the rated value of the device
to be driven may damage the motor or machine.
Match the rating of the device.


‹

This function sets the maximum output frequency in the
constant-torque range of motor 1 or the output
frequency at the rated output voltage. Match the rating
of the motor.

‹

This is a function for motor 1.


Setting range G11S: 25 to 400Hz

P11S: 25 to 120Hz

Note: When the set value of base frequency 1 is higher
than that of maximum output frequency 1, the output
voltage does not increase to the rated voltage because
the maximum frequency limits the output frequency.

Output frequency

F06 Maximum
output voltage 1

Output

voltage

F05 Rated voltage 1

0

F04 Base
frequency 1

F03 Maximum
output frequency

Constant-torque range


‹

This function sets the rated value of the voltage output
to motor 1. Note that a voltage greater than the supply
(input) voltage cannot be output.

‹

This is a function for motor 1.


Setting range 230 V series: 0, 80 to 240V

460 V series: 0, 320 to 480V

Value 0 terminates operation of the voltage regulation
function, thereby resulting in the output of a voltage
proportional to the supply voltage.

Note: When the set value of rated voltage 1 exceeds
maximum output voltage 1, the output voltage does not
increase to the rated voltage because the maximum
output voltage limits the output voltage.

‹

This function sets the maximum value of the voltage

output for motor 1. Note that a voltage higher than the
supply (input) voltage cannot be output.

‹

This is a function for motor 1.


Setting range

230 V series: 80 to 240V

460 V series: 320 to 480V

Note: When the set value of rated voltage 1 (F05) to "0",
this function is invalid.



‹

This function sets the acceleration time for the output

frequency from startup to maximum frequency and the
deceleration time from maximum frequency to operation
stop.



Setting range Acceleration time 1: 0.01 to 3,600 seconds
Deceleration time 1: 0.01 to 3,600 seconds

Acceleration and deceleration times are represented by
the three most significant digits, thereby the setting of
three high-order digits can be set.

Set acceleration and deceleration times with respect to
maximum frequency. The relationship between the set
frequency value and acceleration/deceleration times is
as follows:

Set frequency = maximum frequency

The actual operation time matches the set value.

Outp

ut fr

equen

cy

Acceleration time

Set frequency

Time

Deceleration time

Maximum frequency

Set frequency < maximum frequency
The actual operation time differs from the set value.

Acceleration(deceleration) operation time = set value x
(set frequency/maximum frequency)

Acceleration
operation time

Time

Set frequency

Deceleration time

Acceleration time

Deceleration
operation time

Out

pu

t fr

equenc

y

Maximum frequency

Note: If the set acceleration and deceleration times are
too short even though the resistance torque and moment
of inertia of the load are great, the torque limiting function
or stall prevention function becomes activated, thereby
prolonging the operation time beyond that stated above.

F04

Base frequency 1

F03

Maximum frequency 1

F05

Rated voltage 1

F06

Maximum voltage 1

F07

Acceleration time 1

F08

Deceleration time 1

STOP

FWD

STOP

FWD

F 0 3

M A X H z

- 1

F 0 7

A C C

T I M E 1

F 0 8

D E C

T I M E 1

F 0 4

B A S E H z - 1

F 0 5

R A T E D

V - 1

F 0 6

M A X V -

1

Advertising