Burnout direction – Fujimoto Fuji Differential Pressure Transmitter FKK 4 User Manual

Page 23

Advertising
background image

17

Burnout direction

Used for selecting output at occur-
rence of a fault in the detecting unit.
Burnout direction is selectable un-
der display 2 .

• For selection of NOT USED, press

<1>.

• For selection of OVER SCALE,

press <2>.

• For selection of UNDER SCALE,

press <3>.
The meaning of each condition
above is as follows.

• NOT USED

Not used

(Output hold)
Saturation current = 3.8, 20.8mA

Note) Output value just before the occur-

rence of trouble is given in the out-
put hold mode.

• OVER SCALE

Over scale

(Output 20.8 to 21.6mA)
Saturation current = 3.8, 20.8mA

• UNDER SCALE Under scale

(Output 3.2 to 3.8 mA)
Saturation current = 3.8, 20.8mA

Burnout Current of FCX-CII series
transmitter
Over scale burnout current = 20.8 to
21.6mA
Under scale burnout current=3.2 to
3.8mA
Saturation current=3.8, 20.8mA

CHNG

3

9-2:

BURNOUT

CHANGE

CHNG OK? < ENT/CL >

4

5

6

2

9:BURNOUT

NOT USED
(HOLD)

< INC > < CHANGE >

1

9-2:

BURNOUT

CHANGE

Selection of
burnout direction

(ex)

< ENT > < CL >

CL

CL

CL

CHNG

CHNG

ENT

INC

CL

CL

or

or

2

1

3

3

9-1:

BURNOUT

< 1 > NOT USED
< 2 > OVER SCALE
< 3 > UNDER SCALE

UNDER SCALE

9-4:

BURNOUT

< CHANGE > < CL >

UNDER SCALE
Y.YmA

9-5: BURNOUT

< CL >

Saturate Current
3.8-20.8mA

9-5:

BURNOUT CHNG

< DEC > <ENT > < CL >

UNDER SCALE

UNDER SCALE (burnout current)

Y.YmA

UNDER SCALE

ENT

ENT

ENT

INC

7

8

9

10

CL

CL

9-5:

BURNOUT CHNG

CHNG OK? < ENT/CL >

UNDER SCALE
Y.YmA

9: BURNOUT

< INC > < CHANGE >

UNDER SCALE
Y.YmA

Upon pressing <DEC> or <INC>
burnout current can be changed.
(See above.)

9-7:

BURNOUT

< CL >

Saturate Current

3.8-20.8mA

INC

DEC

Y.YmA
3.8mA
3.7mA
3.6mA
3.5mA
3.4mA
3.3mA
3.2mA

A : CALIBRATE

A : CALIBRATE

Change of Over scale current

21.6mA
21.5mA
21.4mA
21.3mA
21.2mA
21.1mA
21.0mA
20.9mA
20.8mA

INC

DEC