65

PARAMETER SETTING PRIOR TO DELIVERY

The damping value (time constant), function of zero/span adjust screw, output current mode, indicator
scale, cut point, mode below cut point and burnout, have been set prior to delivery as shown in the
following.

Note 1: For span adjustment, HHC should be used. HHC can also be used for zero adjustment.

Note 2: In both the differential pressure transmitter and remote seal type, the output current mode is

set in linear unless it is designated.

Note 3: Burnout direction is selectable from HHC, Hold, Over scale (20.8 to 21.6), under scale (3.2 to

3.8mA).

A3

Item

No.

Damping value

(time constant)

Zero adjust

screw function

Current output mode

Digital indicator scale

(9th digit of code
symbols)

Cut point

(square-root extraction
mode setting)

Mode below cut point

(square-root setting)

Linear

Burnout

To be set by designation

when ordering ( Note 3)

1

2

3

4

5

6

To be set by designating type

when ordering

7.07%

Contents of parameter

No Damping

(= measuring period)

Zero point adjustment possible

To be set by designation

when ordering (Note 2)

7

Linearization function

Invalid