Cautions on impulse piping

• For liquid, the impulse pipes should have an upward slope of 1/10 or more between the

process connection and the transmitter to prevent accumulation of gas, etc. in the detect-
ing unit.

• For gas, the impulse pipes should have a downward slope of 1/10 or more between the

process connection and transmitter to prevent accumulation of moisture, etc. in the de-
tecting unit.

• Do not bent the impulse pipes acutely near the pressure outlet port, to prevent gas or drain

from staying in the pipe.

• Take care not to apply an excessive force to the transmitter during connection.

• In order to prevent vibration of the transmitter body and capillary from interfering with

output, the transmitter body should be installed at a vibration-free place and the capillary
should be fixed to a stable support.

• The impulse pipes used should be suitable for the working temperature, pressure, etc.

• When the measuring fluid is likely to freeze in the cover of the measurement chamber,

the cover needs to be warmed up with steam or a heater.