Fujimoto Fuji Differential Pressure Transmitter FKK 4 User Manual

Page 30

Advertising
background image

24

G-2 : DISP. CHANGE
LRV: 4mA=±YYYYYY
URV: 20mA=±ZZZZZZ
< LRV >< URV ><CL>

11

12

3

11

13

1

2

3

CL

URV

LRV

CL

11

CL

URV

ENT

ENT

GP, AP, LL
(liquid Level)

G-2: DISP. CHANGE
Can’t proceed.
XMTR doesn't
support. < CL >

CL

A

G-2 : DISP. CHANGE
LRV: 4mA=±YYYYYY
URV: 20mA=±ZZZZZZ
< ENT >< URV ><CL>

Already set value
of transmitter

Already set value of transmitter

= PRESS./LEVEL/FLOW

16

11

19

CL

ENT

CHNG

G-3 : DISP. CHANGE
DispUNIT=UUUUUUU

(

)

<CHNG><ENT><CL>

18

17

CL

ENT

INC

G-5 : DISP. CHANGE
DispUNIT=UUUUUUU
(NEXT XXXXXXX)
<INC><ENT><CL>

17

16

CL

G-4 : DISP. CHANGE
<1>PRESS.<3>FLOW
<2>LEVEL
<1><2><3><CL>

14

G-2 : DISP. CHANGE
LRV: 4mA=±YYYYYY
URV: 20mA=±ZZZZZZ
SET OK?< ENT ><CL>

11

CL

15

G-2 : DISP. CHANGE
LRV: 4mA=±YYYYYY
URV: 20mA=±ZZZZZZ
SETTING ERR <CL>

13

11

12

CL

URV

ENT

G-2 : DISP. CHANGE
LRV: 4mA=±YYYYYY
URV: 20mA=±ZZZZZZ
< ENT >< URV ><CL>

<1>PRESS

(a)

18

17

CL

ENT

INC

G-5 : DISP. CHANGE
DispUNIT=UUUUUUU
(NEXT XXXXXXX)
<INC><ENT><CL>

19

17

CL

ENT

G-5 : DISP. CHANGE
DispUNIT=UUUUUUU

SET OK?<ENT><CL>

20

11

CL

ENT

G-6 : DISP. CHANGE
±YYYYYY/±ZZZZZZ
UUUUUUU
CHNG OK?<ENT/CL>

21

2

G-7 : DISP. CHANGE
±YYYYYY/±ZZZZZZ
UUUUUUU

<2>LEVEL

<3>FLOW

(b)

18

17

17

40

40

CL

ENT

INC

G-5 : DISP. CHANGE
DispUNIT=UUUUUUU
(NEXT XXXXXXX)
<INC><ENT><CL>

19

17

CL

ENT

G-5 : DISP. CHANGE
DispUNIT=UUUUUUU

SET OK?<ENT><CL>

20

11

CL

ENT

G-6 : DISP. CHANGE
±YYYYYY/±ZZZZZZ
UUUUUUU
CHNG OK?<ENT/CL>

21

B

G-7 : DISP. CHANGE
±YYYYYY/±ZZZZZZ
UUUUUUU

DP

(c)

(UNIT=PRESS. LEVEL)

(UNIT=FLOW)

<DISP. UNIT CHANGE>

(a)
mmH

2

O

cmH

2

O

mH

2

O

g/cm

2

kg/cm

2

Pa
hPa
kPa
MPa
mbar
bar
psi
inH

2

O

ftH

2

O

mmAq
cmAq
mAq
mmWC
cmWC
mWC
mmHg
cmHg
mHg
inHg
(Torr)
(atm)

(b)
mm
cm
m
in
ft

(c)
Nm

3

/s

Nm

3

/min

Nm

3

/h

Nm

3

/d

m

3

/s

m

3

/min

m

3

/h

m

3

/d

t/s
t/min
t/h
t/d
l/s
l/min
l/h
l/d
gal/s
gal/min
gal/h
gal/d
ft

3

/s

ft

3

/min

ft

3

/h

ft

3

/d

bbl/s
bbl/min
bbl/h
bbl/d

( ) is available
for GP and AP.

(C) is available for DP.

NC

DEC

When setting the actual-scale display,
first select <2> ACTUAL DISP in 3 .
Next, after setting the actual-scale
display value ( 11 to 14 ), perform the
actual-scale display unit setting
( 16 to 19 ).
In case of pressure transmitter,
absolute pressure transmitter and
level transmitter, the flow units can-
not be set as shown in 17 .
After making sure of the setting of the
actual scale display 20 , enter the
[ENT] and then data is written in the
transmitter.