It should be noted that leakage of fluid from the wetted parts would affect
the performance due to the progress of corrosion.

Important

Caution of installation

• Restriction on H

1

Liquid level is not proportional to the transmitter output at some points inside
the seal diaphragm.
Therefore, H

1

should be set higher than the value shown in the table below.

• In order to prevent vibration, the transmitter body should be installed at a

vibration-free place.

• Do not shock the seal diaphragm by hitting hard object against it, for example.

• Take care not to apply an excessive force to the flange during connection.

Minimum value of H

1

Flange size

Non projection type

Projection type

DN40 / 1 1/2”

30mm

DN50 / 2”

30mm

30mm

DN80 / 3”

55mm

40mm

DN100 / 4”

55mm

55mm