Urv = ρ.(h – Fujimoto Fuji Differential Pressure Transmitter FKK 4 User Manual

Page 58

Advertising
background image

52

Typical example of piping

Level measurement of open tank
Leave the below pressure side of the transmitter open to atmosphere.

Level circulation formula

LRV =

ρ.H

1

URV =

ρ.(H

1

+h)

LRV = low limit of measurement (0%)

URV = high limit of measurement (100%)

ρ = measuring liquid density

H

1

= Liquid level

h = liquid level change

6.2.3

Piping of level transmitter type : FKP for open tank

Seal on mounting flange face

When mounting the flange on the pressure side, a gasket should be inserted as
follows.

0

20

40

60

80

100

Transmitter flange

Process side flange

Gasket

On the projection type, be sure to use a gasket with an internal diameter larger

than the flange to prevent the gasket form touching the seal diaphragm.

Important

Connecting method of the mounting flange

Thighten bolts of mounting flange and process flange in a diagonal order and
about three cycles.

Removal of protective cap from process connection port

The process connection port on the low pressure side is fitted with a protective
cap. Before piping, remove the cap carefully. When removing the cap,
carrefully protect the threaded portion and sealing face from damage.

Connection of transmitter and impulse pipe

After connection, close the stop valve of the transmitter in order to prevent
foreign materials from entering the inside.